Service Manual
Table Of Contents
- Important Safety Information
- I. Construction and Water/Refrigeration Circuit Diagram
- II. Sequence of Operation and Service Diagnosis
- III. Controls and Adjustments
- A. Control Board Layout
- B. LED Lights and Audible Alarm Safeties
- C. Settings and Adjustments
- 1. Default Dip Switch Settings
- 2. Harvest Time (S4 dip switch 1 & 2)
- 3. Pump-Out Time/Harvest Time During Pump-Out (S4 dip switch 3 & 4)
- 4. Pump-Out Frequency Control (S4 dip switch 5)
- 5. Harvest Pump Time Duration (Harvest Assist) (S4 dip switch 6)
- 6. Harvest Pump Time (Harvest Assist)/Freeze-Time Correction (S4 dip switch 7)
- 7. Factory Use (S4 dip switch 8)
- 8. Freeze Timer (S4 dip switch 9 & 10)
- 9. Float Switch Selector (S5 dip switch 1)
- 10. Refill Counter (S5 dip switch 2 and 3)
- IV. Refrigeration Circuit and Component Service Information
- V. Maintenance
- VI. Preparing the Appliance for Periods of Non-Use
- VII. Disposal
- VIII. Technical Information
31
No Ice Production - Possible Cause
15. Pump Motor a) Motor winding open.
b) Bearing worn out or locked rotor.
c) Defective capacitor.
d) Mechanical seal worn out.
16 Thermostatic Expansion Valve a) Bulb loose.
b) Operating erratically.
1 7. Liquid Line Valve a) Closed in freeze cycle.
b) Open in harvest cycle.
18. Fan Motor a) Motor winding open.
b) Bearing worn out or locked rotor.
c) Defective capacitor.
19. Water System a) Water leaks causing short freeze time.
2. Low Ice Production
Low Ice Production - Possible Cause
1. Appliance in Freeez-Time
Correction Cycle
a) See "II.C.Freeze-Time Correction Cycle."
Long Harvest Cycle
1. Evaporator a) Scaled up.
2. Spray Tubes, Spray Guides,
Cube Guides, Splash Guard, or
Separator A
a) Dirty.
b) Out of position.
3. Refrigerant Charge a) Low.
4. Water Supply a) Low water pressure.
b) External water lters clogged.
c) Insufficient water line size.
Minimum 3/8" Nominal ID (10 mm Nominal OD in the EU) water
tubing or equivalent.
d) Too cold.
5. Control Board
See "II.D. Control Board Check"
a) Thermistor connection loose (K3).
b) Defective.
6. Thermistor
See "II.G. Thermistor Check"
a) Loose, disconnected, or defective.
7. Hot Gas Valve a) Erratic or closed.
8. Inlet Water Valve a) Screen or orice clogged.
9. Compressor a) Inefficient or off.
10. Liquid Line Valve a) Erratic or open.
11. Thermostatic Expansion Valve a) Defective.
Short Freeze Cycle
1. Low Water Supply a) Water lters clogged.
2. Inlet Water Valve a) Screen or orice clogged.