Service Manual
Table Of Contents
- Important Safety Information
- I. Construction and Water/Refrigeration Circuit Diagram
- II. Sequence of Operation and Service Diagnosis
- III. Controls and Adjustments
- A. Control Board Layout
- B. LED Lights and Audible Alarm Safeties
- C. Settings and Adjustments
- 1. Default Dip Switch Settings
- 2. Harvest Time (S4 dip switch 1 & 2)
- 3. Pump-Out Time/Harvest Time During Pump-Out (S4 dip switch 3 & 4)
- 4. Pump-Out Frequency Control (S4 dip switch 5)
- 5. Harvest Pump Time (Harvest Assist) (S4 dip switch 6)
- 6. Harvest Pump Time (Harvest Assist)/Freeze-Time Correction (S4 dip switch 7)
- 7. Factory Use (S4 dip switch 8)
- 8. Freeze Timer (S4 dip switch 9 & 10)
- 9. Float Switch Selector (S5 dip switch 1)
- 10. Refill Counter (S5 dip switch 2 and 3)
- 11. Minimum Harvest Time (S5 dip switch 4)
- 12. Anti-Slush (S5 dip switch 5)
- IV. Refrigeration Circuit and Component Service Information
- V. Maintenance
- VI. Preparing the Icemaker for Periods of Non-Use
- VII. Disposal
- VIII. Technical Information
23
d) PM Diagnosis: Check for 115VAC at X12 relay #6 (P) to neutral(W). If 115VAC is not
present, see "b) CB Diagnosis" above. Next, check for 115VAC at X12 relay #4(Y)
to neutral (W). If 115VAC is not present, conrm X12 relay is energized. If X12 relay
is de-energized, see "c) X12 Relay Diagnosis:" above. If X12 relay is energized
and 115VAC is present at X12 relay #6 (P) and not at X12 relay #4 (Y), replace X12
relay. If 115VAC is present at X12 relay #4 (Y) and PM is de-energized, check PM
capacitor, motor winding, wiring connections, and impeller for binding.
e) DV Diagnosis: Check for 115VAC at X12 relay #5 (P) to neutral (W) and at X12relay
#3 (GY) to neutral (W). If 115VAC is not present at X12 relay #5 (P), see "b) CB
Diagnosis:" above. If 115VAC is present at X12 relay #5 (P) and not at X12 relay
#3(GY), conrm X12 relay is energized. If X12 relay is de-energized,
see "c) X12 Relay Diagnosis:" above. If X12 relay is energized and 115VAC
is present at X12 relay #5 (P) and not at X12 relay #3 (GY), replace X12 relay.
If115VAC is present at X12 #3 (GY) and DV is de-energized, check DV coil
continuity, make sure the drain line is not clogged and that DV is clean and operating
properly.
8) Normal Harvest Cycle – Same as the initial harvest cycle. Return to step 5a) above.
Note: Appliance continues to cycle until BC is satised or power is switched off. The
appliance always restarts at the 1-min. ll cycle.
2. Shutdown Diagnosis
1) See "II.E. Bin Control Check."
3. Freeze-Time Correction Cycle Diagnosis
1) See "II.C. Freeze-Time Correction Cycle (90 min.)."
Legend: BC–bin control; CB–control board; Comp–compressor; CR–compressor relay;
CT–control transformer; CV–check valve; FM–fan motor; FMR–fan motor remote;
FS–oat switch; HGV–hot gas valve; HM–headmaster (C.P.R.); HPS–high-pressure
switch; L LV–liquid line valve; PM–pump motor; TXV–thermostatic expansion valve;
WRV–water regulating valve; WV–inlet water valve