Service Manual
Table Of Contents
- Important Safety Information
- I. Construction and Water/Refrigeration Circuit Diagram
- II. Sequence of Operation and Service Diagnosis
- III. Controls and Adjustments
- A. Control Board Layout
- B. LED Lights and Audible Alarm Safeties
- C. Settings and Adjustments
- 1. Default Dip Switch Settings
- 2. Harvest Time (S4 dip switch 1 & 2)
- 3. Pump-Out Time/Harvest Time During Pump-Out (S4 dip switch 3 & 4)
- 4. Pump-Out Frequency Control (S4 dip switch 5)
- 5. Harvest Pump Time (Harvest Assist) (S4 dip switch 6)
- 6. Harvest Pump Time (Harvest Assist)/Freeze-Time Correction (S4 dip switch 7)
- 7. Factory Use (S4 dip switch 8)
- 8. Freeze Timer (S4 dip switch 9 & 10)
- 9. Float Switch Selector (S5 dip switch 1)
- 10. Refill Counter (S5 dip switch 2 and 3)
- 11. Minimum Harvest Time (S5 dip switch 4)
- 12. Anti-Slush (S5 dip switch 5)
- IV. Refrigeration Circuit and Component Service Information
- V. Maintenance
- VI. Preparing the Icemaker for Periods of Non-Use
- VII. Disposal
- VIII. Technical Information
18
5a) Initial Harvest Cycle – LEDs 1, 4, and 2 are on. WV and X11 relay continue. Comp,
FMR, HGV, and X10 relay energize. CBmonitors the warming of the evaporator via
the thermistor located on the suction line. When the thermistor reaches 48°F (9°C),
CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest
timer (S4 dip switch 1 & 2 and S5dip switch 4). WV and X11 relay are energized
during harvest for a maximum of 6 min. or the length of harvest minus HPT setting
(S4dip switch 6), whichever is shorter. See step 5b below.
a) Comp Diagnosis: Check that evaporator is warming. Ifnot, conrm that Comp
energizes. If not, check for 115VAC at CB K1 #1 (V) or #9 (V) to neutral (W).
If115VAC is not present, check for 115VAC at CB K1 #7 (BR) or #10 (BR) to neutral
(W). If115VAC is present at #7 (BR) or #10 (BR) and not at #1 (V) or #9 (V), replace
CB. If 115VAC is present, check for 115VAC at CR solenoid. If 115VAC is present,
conrm contacts are closed. If not, replace CR. If CR contacts are closed, check
Comp external overload, Comp start and run capacitors, Comp start relay, and
Comp motor winding.
b) HGV Diagnosis: If Comp is energized and evaporator is not warming, check that
HGV energizes and opens. Check for 115VAC at CB K1 #2 (P) to neutral (W).
If115VAC is not present and LED 2 is on, replace CB. If 115VAC is present, check
for 115VAC at HGV coil and check HGV coil continuity. Replace as needed.
c) LLV Diagnosis: Conrm that LLV is de-energized and closed (not bypassing).
Ifenergized, replace CB. If de-energized and bypassing, replace LLV.
d) WRV Diagnosis: Conrm WRV is not leaking by. If WRV is leaking by, conrm HGV
is open and LLV is closed. Next, check for proper refrigerant pressures. If refrigerant
pressures are correct, adjust or replace WRV. See "IV.C. Water Regulating Valve
Adjustment (water-cooled model)."