Service Manual
Table Of Contents
- Important Safety Information
- I. Construction and Water/Refrigeration Circuit Diagram
- II. Sequence of Operation and Service Diagnosis
- III. Controls and Adjustments
- A. Control Board Layout
- B. LED Lights and Audible Alarm Safeties
- C. Settings and Adjustments
- 1. Default Dip Switch Settings
- 2. Harvest Time (S4 dip switch 1 & 2)
- 3. Pump-Out Time/Harvest Time During Pump-Out (S4 dip switch 3 & 4)
- 4. Pump-Out Frequency Control (S4 dip switch 5)
- 5. Harvest Pump Time (Harvest Assist Duration) (S4 dip switch 6)
- 6. Harvest Pump Time (Harvest Assist) (S4 dip switch 7)
- 7. Factory Use (S4 dip switch 8)
- 8. Freeze Timer (S4 dip switch 9 & 10)
- 9. Float Switch Selector (S5 dip switch 1)
- 10. Refill Counter (S5 dip switch 2 and 3)
- 11. Minimum Harvest Time (S5 dip switch 4)
- 12. Slush Control (S5 dip switch 5)
- IV. Refrigeration Circuit and Component Service Information
- V. Maintenance
- VI. Preparing the Appliance for Periods of Non-Use
- VII. Disposal
- VIII. Technical Information
22
e) X13 Relay Diagnosis - If115VAC is present at X12 terminal #3 (DBU) to neutral and
PM and DV are not energized, check for 115VAC at X13 terminal #8 (DBU) to neutral
(W). If115VAC is present and X13 relay is de-energized, replace X13 relay.
(1) For PM and X13 Relay: If115VAC is present at X13 terminal #8 (DBU), check
for 115VAC at X13relay #6 (BK) and X13 relay #4 (Y) to neutral (W). If115VAC
is present at X13 relay #6 (BK) and not at X13 relay #4 (Y), replace X13 relay
(contacts sticking open). If 115VAC is present at X13 relay #4 (Y) and PM is not
energized, check PM capacitor, motor winding, and impeller for binding.
(2) For DV and X13 Relay: If115VAC is present at X13 terminal #8 (DBU), check for
115VAC at X13 relay #5 (DBU) and X13 relay #3 (W/BU) to neutral (W). If115VAC
is present at X13relay #5 (DBU) and not at X13 relay #3(W/BU), replace X13
relay (contacts sticking open). If 115VAC is present at X13 relay #3 (W/BU) and
DV is de-energized, check DV coil continuity, make sure the drain line is not
clogged and that DV is clean and operating properly.
8) Normal Harvest Cycle – Same as the initial harvest cycle. Return to step 5a) above.
Note: Appliance continues to cycle until BC is satised or power is switched off. The
appliance always restarts at the 1-min. ll cycle.
2. Shutdown Diagnosis
1) See "II.D. Bin Control Check."
Legend: BC–bin control; CB–control board; Comp–compressor; CR–compressor relay;
CT–control transformer; CV–check valve; DV–drain valve; FM–fan motor;
FMR–fan motor remote; FS–oat switch; HGV–hot gas valve;
HM–headmaster (C.P.R.); HPS–high-pressure switch; L LV–liquid line valve;
PM–pump motor; TXV–thermostatic expansion valve; WRV–water regulating valve;
WV–inlet water valve