b) Connection to a Closed Loop System
Condenser water supply inlet is 1/2” female pipe thread (FPT). A minimum of 1/4”
nominal ID copper water tubing or equivalent is required for the condenser water supply
line.
• Condenser return outlet is 1/2” FPT. A minimum of 1/4” nominal ID copper water tubing or
equivalent is required for the condenser return line.
• Shut-off valves and drain valves should be installed at both the condenser water supply
inlet and condenser return outlet.
The water supply to the condenser should not drop below 4 GPM.
The pressure differential between the condenser water supply inlet and condenser return
outlet must be no less than 10 PSIG.
When using a glycol blend, the solution mixture should be less than 30% glycol.