II. Sequence of Operation and Service Diagnosis
A. Sequence of Operation Flow Chart
1. Operation Flow Chart
FS check
1 to 3-min. harvest timer in
control (S4 dip switch 1 & 2)
Legend:
BC–bin control
Comp–compressor
DV–drain valve
FM–fan motor
FMR–fan motor-remote
FS–oat switch
HGV–hot gas valve
LLV –liquid line valve
PM–pump motor
WV–inlet water valve
Components Energized when the Control Switch is in the "PUMP" Position
When the control switch is in the "PUMP" position power is supplied to the pump motor. Water tank contents then ows over the outside of the
evaporator plate assembly. Note: Water tank contents does not ow inbetween the evaporator plates.
Operation Flow Chart
1. 1-Minute
Fill Cycle
Cycle
Steps
2. Harvest Cycle
WV time: 6 min. or the length of harvest minus 50 sec.
(S4 dip switch 7), whichever is shorter. Do not adjust S4
dip switch 7 out of the factory position.
• Max. harvest time: 20 min.
Thermistor
in control
3. Freeze Cycle
• Min. freeze time: 5 min.
• Max. freeze time: freeze timer setting (S4 dip
switch 9 & 10)
• Freeze-Time monitoring for Freeze-Time
Correction starts at 2nd freeze cycle.
FS in control
4. Pump-Out Cycle
• Factory set for every 10th
cycle
(S4 dip switch 5)
• Pump motor stops for
2 sec., then reverses for
10/20 sec.
(S4 dip switch 3 & 4)
WV energized
FS open
Comp energized
FMR energized
HGV energized
WV energized
Thermistor temperature reaches
48°F (9°C) (3.9 kΩ or less).
Harvest timer starts.
FS open
Comp energized
FM energized
FMR energized
PM energized
LLV energized
HGV de-energized
FS closed
Comp energized
DV energized
FMR energized
HGV energized
PM de-energizes for 2 sec.,
then energizes for 10/20 sec.
FM de-energized
LLV de-energized
FS check
Startup
If FS is open, Comp stops and cycle returns to
1-Min. ll.
5-min.
minimum
freeze timer in
control
FS closed
FS opens or freeze
timer terminates
50 sec.
PM energized
WV de-energized
Harvest Pump
Timer
Anti-Slush
Thermistor temperature
reaches 36°F (2.2°C)
(5.8 kΩ).
PM de-energized for
10 sec.
Freeze Time Differential Exceeded.
Initiate Freeze-Time Correction Cycle.
See "II.A.3. Freeze-Time Correction Cycle.
Components Energized when the Control Switch is in the "ON" or "PUMP" position and the Mode Switch
is in the "CLEAN" Position
When the control switch is in the "ON" position and the mode switch is in the "CLEAN" position power is supplied to the control board K9 connector. The control board
then initiates a clean/sanitze program. See the maintenance label on the top cover or the instruction manual for details.
When the control switch is in the "PUMP" position and the mode switch is in the "CLEAN" position, only the pump motor energizes and circulates water tank contents
over outside of evaporator plate assembly as the control board power supply has been disconnected. The Clean/Sanitize program cannot initiate in this scenario.