Service Manual
Table Of Contents
- Important Safety Information
- I. Construction and Water/Refrigeration Circuit Diagram
- II. Sequence of Operation and Service Diagnosis
- III. Controls and Adjustments
- A. Control Board Layout
- B. LED Lights and Audible Alarm Safeties
- C. Settings and Adjustments
- 1. Default Dip Switch Settings
- 2. Harvest Time (S4 dip switch 1 & 2)
- 3. Pump-Out Time/Harvest Time During Pump-Out (S4 dip switch 3 & 4)
- 4. Pump-Out Frequency Control (S4 dip switch 5)
- 5. Harvest Pump Time (Harvest Assist) (S4 dip switch 6)
- 6. Harvest Pump Time (Harvest Assist)/Freeze-Time Correction (S4 dip switch 7)
- 7. Factory Use (S4 dip switch 8)
- 8. Freeze Timer (S4 dip switch 9 & 10)
- 9. Float Switch Selector (S5 dip switch 1)
- 10. Refill Counter (S5 dip switch 2 and 3)
- IV. Refrigeration Circuit and Component Service Information
- V. Maintenance
- VI. Preparing the Icemaker for Periods of Non-Use
- VII. Disposal
- VIII. Technical Information
- A. Specification and Performance Data
- 1. KM-1301SAJ
- 2. KM-1301SAJ3
- 3. KM-1301SWJ
- 4. KM-1301SWJ3
- 5. KM-1301SRJ with URC-14F
- 6. KM-1301SRJ3 with URC-14F
- 7. KM-1601SAJ
- 8. KM-1601SAJ3
- 9. KM-1601SWJ
- 10. KM-1601SWJ3
- 11. KM-1601SRJ with URC-22F
- 12. KM-1601SRJ3 with URC-22F
- 13. KM-1900SAJ
- 14. KM-1900SAJ3
- 15. KM-1900SWJ
- 16. KM-1900SWJ3
- 17. KM-1900SRJ with URC-22F
- 18. KM-1900SRJ3 with URC-22F
- 19. KM-2200SWJ3
- 20. KM-2200SRJ3 with URC-22F
- 21. KM-2600SWJ3
- 22. KM-2600SRJ3 with URC-23F
- B. Wiring Diagrams
- A. Specification and Performance Data
24
f) Refrigerant Pressures, HM, and TXV Diagnosis: If evaporator is still not cooling,
check refrigerant pressures. See "VIII.A. Specication and Performance Data."
Next, check HM operation. If refrigeration pressures are above HM setpoint and
HMis bypassing, replace HM. Check TXV for proper operation. Remove TXV bulb
and hold it in your hand, refrigerant low-side pressure should rise, place TXV bulb in
ice water, refrigerant low-side pressure should drop. A 10 to 15 pound pressure swing
between warm and cold conditions indicate a good TXV. If a 10 to 15 pound swing is
not present, replace TXV.
g) WRV Diagnosis: WRV is factory set and generally no adjustment is required.
IfWRV fails to open in freeze, check for proper refrigerant pressures. See "VIII.A.
Specication and Performance Data." If refrigerant pressures are correct and WRV
does not open, adjust or replace as needed. See "IV.C. Water Regulating Valve
Adjustment (water-cooled models)."
h) Freeze Termination Diagnosis: After 5 min. in freeze, disconnect CB K5 FS
connector. 15 sec. later appliance should switch out of the freeze cycle (15 second
delay after FS opens before terminating the freeze cycle). If appliance remains in
freeze longer than 15 sec. after FS removed, replace CB. If appliance switches with
FS removed but would previously not switch out of freeze with FS connected (long
freeze - 3 beep alarm), see "II.E. Float Switch Check and Cleaning."
Note: Normal freeze cycle will last 20 to 40 min. depending on model and conditions.
Cycle times and pressures should follow performance data provided in this
manual. See "VIII.A. Specication and Performance Data."
i) Short Freeze Cycle Diagnosis: Conrm water tank lls and overows during ll and
harvest cycles. If not, check water supply lters, shut-off valve, WV screen. Ifwater
tank empties before 5 min. timer terminates and freeze cycle is short, check that CV
is not leaking by (water owing down the potable drain). If CV is leaking by, remove
and clean CV, replace rubber seat and spring if necessary. If water tank is full, see
"II.E. Float Switch Check and Cleaning." for erratic FS.
7) Pump-Out Cycle – LEDs 1, 3, and 2 are on (10/20 second pump-out). Timing of the
rst pump-out is determined by S4 dip switch 5. See the table below.
"J" Control Board Settings
S4 Dip
Switch
Setting
Pump-Out
Frequency
1st Pump-Out
"J" Control Board
No. 5
OFF Every 10 cycles After 11th freeze cycle
ON Every cycle After 2nd freeze cycle
Comp, FM* (if connected to CB K1 connector pin #9), and FMR continue, HGV
energizes. If S4dip switch 3 & 4 are set to 3 off and 4 on, LED 4 turns on and WV
and X11 relay energize, energizing X10relay. NOTICE!S4dip switch 3 & 4 must
not be set to 3 off and 4 on. Otherwise, PM will rotate in freeze cycle direction
instead of pump-out direction. FM (if connected to CB K1 connector pin #3) and
LLVde-energize. PM stops for 2 sec., then reverses for 10/20 sec. depending on
pump-out timer (S4dip switch 3 & 4) setting. When the pump-out timer terminates,