Service Manual
Table Of Contents
- Important Safety Information
- I. Construction and Water/Refrigeration Circuit Diagram
- II. Sequence of Operation and Service Diagnosis
- III. Controls and Adjustments
- A. Control Board Layout
- B. LED Lights and Audible Alarm Safeties
- C. Settings and Adjustments
- 1. Default Dip Switch Settings
- 2. Harvest Time (S1 dip switch 1 & 2)
- 3. Pump-Out Time/Harvest Time During Pump-Out (S1 dip switch 3 & 4)
- 4. Pump-Out Frequency Control (S1 dip switch 5 & 6)
- 5. Harvest Pump Time Duration (Harvest Assist) (S1 dip switch 7 & 8)
- 6. Freeze Timer (S1 dip switch 9 & 10)
- 7. Pump-Out/Drain Selector (S2 dip switch 1)
- 8. Harvest Promotion Control (S2 dip switch 2)
- 9. Minimum Harvest Time (S2 dip switch 3)
- 10. Harvest Completion Detection Control (S2 dip switch 4)
- 11. Overfreeze Detection Control (S2 dip switch 5)
- 12. Slush Control (S2 dip switch 6)
- IV. Refrigeration Circuit and Component Service Information
- V. Maintenance
- VI. Preparing the Appliance for Periods of Non-Use
- VII. Disposal
- VIII. Technical Information
37
2. Harvest Time (S1 dip switch 1 & 2)
The harvest timer starts counting when the thermistor reaches 48°F (9°C) at the
evaporator outlet and the control board reads 3.9 kΩ from the thermistor. The harvest
timer is factory set, and generally no adjustment is required. However, a setting longer
than the factory setting may be advised in cases where the drain provided at harvest
needs to be prolonged for extra cleaning. Note that the pump-out timer (S1 dip switch
3 & 4) acts in place of the harvest timer during cycles with a pump out. For details, see
"III.C.3. Pump-Out Timer (S1 dip switch 3& 4)."
Note: On models with a pump-out every cycle, the harvest timer is only relevant during
the initial harvest cycle since a pump out occurs every cycle thereafter.
S1 Dip Switch Setting Time
(sec.)
No. 1 No. 2
OFF OFF 60
ON OFF 90
OFF ON 120
ON ON 180
3. Pump-Out Time/Harvest Time During Pump-Out (S1 dip switch 3 & 4)
When a pump-out is called for, the pump motor stops for 2 seconds, then the pump
motor and drain valve energize. Water is removed from the bottom of the water tank
and sent down the drain. The pump-out drains the water tank for the time determined
by the pump-out timer. The pump-out timer also acts in place of the harvest timer during
cycles with a pump-out. The pump-out timer is factory set, and generally no adjustment
is required. The pump-out timer control can be set to pump-out for 10 or 20 seconds.
During pump-out cycles minimum harvest time is based on times given in the
table below.
S1 Dip Switch Setting Time (sec.)
No. 3 No. 4 T1 T2
OFF OFF 10 120
ON OFF 20 160
OFF ON 20 120
ON ON 20 180
T1: Time to drain the water tank
T2: Harvest timer at pump out