Service Manual
Table Of Contents
- Important Safety Information
- I. Construction and Water/Refrigeration Circuit Diagram
- II. Sequence of Operation and Service Diagnosis
- III. Controls and Adjustments
- A. Control Board Layout
- B. LED Lights and Audible Alarm Safeties
- C. Settings and Adjustments
- 1. Default Dip Switch Settings
- 2. Harvest Time (S1 dip switch 1 & 2)
- 3. Pump-Out Time/Harvest Time During Pump-Out (S1 dip switch 3 & 4)
- 4. Pump-Out Frequency Control (S1 dip switch 5 & 6)
- 5. Harvest Pump Time Duration (Harvest Assist) (S1 dip switch 7 & 8)
- 6. Freeze Timer (S1 dip switch 9 & 10)
- 7. Pump-Out/Drain Selector (S2 dip switch 1)
- 8. Harvest Promotion Control (S2 dip switch 2)
- 9. Minimum Harvest Time (S2 dip switch 3)
- 10. Harvest Completion Detection Control (S2 dip switch 4)
- 11. Overfreeze Detection Control (S2 dip switch 5)
- 12. Slush Control (S2 dip switch 6)
- IV. Refrigeration Circuit and Component Service Information
- V. Maintenance
- VI. Preparing the Appliance for Periods of Non-Use
- VII. Disposal
- VIII. Technical Information
30
Freeze-Up - Possible Cause
Freeze Cycle
1. Evaporator a) Scaled up.
b) Damaged.
2. Spray Tubes and/or Spray
Guides
a) Dirty.
b) Out of position.
3. Refrigerant Charge a) Low.
4. Control Board
See "II.C. Control Board Check"
a) Freeze timer (S1 dip switch 9 & 10) set incorrectly.
b) Defective.
5. Inlet Water Valve a) Leaking by.
6. Float Switch
See "II.E. Float Switch Check
and Cleaning"
a) Float does not move freely.
b) Defective.
7. Pump Motor a) RPM too slow.
b) Impeller damaged.
8. Thermostatic Expansion Valve
(KM-161 B_J Models)
a) Bulb loose or defective.
3. Low Ice Production
Low Ice Production - Possible Cause
Long Harvest Cycle
1. Evaporator a) Scaled up.
2. Spray Tubes and/or Spray
Guides
a) Dirty.
b) Out of position.
3. Refrigerant Charge a) Low.
4. Water Supply a) Low water pressure.
b) External water lters clogged.
c) Insufficient water line size.
Minimum 1/4" Nominal ID (6 mm Nominal OD in the EU) water
tubing or equivalent.
d) Too cold.
5. Control Board
See "II.C. Control Board Check"
a) Thermistor connection loose (K3).
b) Defective.
6. Thermistor
See "II.F. Thermistor Check"
a) Loose, disconnected, or defective.
7. Hot Gas Valve a) Erratic or closed.
8. Inlet Water Valve a) Screen or orice clogged.
9. Compressor a) Inefficient or off.
10. Thermostatic Expansion Valve
(KM-161 B_J Models)
a) Defective.