Service Manual
Table Of Contents
- Important Safety Information
- I. Construction and Water/Refrigeration Circuit Diagram
- II. Sequence of Operation and Service Diagnosis
- III. Controls and Adjustments
- A. Control Board Layout
- B. LED Lights and Audible Alarm Safeties
- C. Settings and Adjustments
- 1. Default Dip Switch Settings
- 2. Harvest Time (S1 dip switch 1 & 2)
- 3. Pump-Out Time/Harvest Time During Pump-Out (S1 dip switch 3 & 4)
- 4. Pump-Out Frequency Control (S1 dip switch 5 & 6)
- 5. Harvest Pump Time Duration (Harvest Assist) (S1 dip switch 7 & 8)
- 6. Freeze Timer (S1 dip switch 9 & 10)
- 7. Pump-Out/Drain Selector (S2 dip switch 1)
- 8. Harvest Promotion Control (S2 dip switch 2)
- 9. Minimum Harvest Time (S2 dip switch 3)
- 10. Harvest Completion Detection Control (S2 dip switch 4)
- 11. Overfreeze Detection Control (S2 dip switch 5)
- 12. Slush Control (S2 dip switch 6)
- IV. Refrigeration Circuit and Component Service Information
- V. Maintenance
- VI. Preparing the Appliance for Periods of Non-Use
- VII. Disposal
- VIII. Technical Information
28
H. Diagnostic Tables
1. No Ice Production
No Ice Production - Possible Cause
1. Power Supply a) Off, blown fuse, or tripped breaker.
b) Unplugged or loose connection.
c) Not within specications.
2. Fuse (Control Box) a) Blown.
3. Control Switch a) In "OFF" or "SERVICE" position.
b) Bad contacts.
4. High-Pressure Switch
(KM-161 B_J Models)
a) Dirty condenser.
b) Fan motor not operating.
c) Refrigerant overcharged.
d) Bad contacts.
e) Refrigerant lines or components plugged.
f) HGV defective.
5. Control Transformer
(115VAC/10.5VAC)
a) Coil winding open or shorted.
6. Control Board
See "II.C. Control Board Check"
a) In alarm.
b) CB "POWER OK" LED ashing (bin full).
c) Defective.
7. Bin Control
See "II.D. Bin Control Check"
a) Tripped with bin lled with ice.
b) Actuator does not move freely.
c) Defective.
8. Water Supply a) Water supply off or improper water pressure.
b) External water lters clogged.
9. Inlet Water Valve a) Screen or orice clogged.
b) Coil winding open.
c) Water valve open in freeze cycle.
10. Float Switch
See "II.E. Float Switch Check
and Cleaning"
a) Float does not move freely.
b) Defective.
11. Compressor a) Compressor relay contacts bad or coil winding open.
b) Start capacitor defective.
c) External protector open.
d) Start relay contacts bad or coil winding open.
e) Compressor defective.
12. Hot Gas Valve a) Closed in harvest cycle.
b) Open in freeze cycle.
13. Thermistor
See "II.F. Thermistor Check"
a) Loose, disconnected, or defective.
14. Pump Motor a) Motor winding open.
b) Bearing worn out or locked rotor.
c) Defective capacitor.
d) Mechanical seal worn out.