Service Manual
Table Of Contents
- Important Safety Information
- I. Construction and Water/Refrigeration Circuit Diagram
- II. Sequence of Operation and Service Diagnosis
- III. Controls and Adjustments
- A. Control Board Layout
- B. LED Lights and Audible Alarm Safeties
- C. Settings and Adjustments
- 1. Default Dip Switch Settings
- 2. Harvest Time (S1 dip switch 1 & 2)
- 3. Pump-Out Time/Harvest Time During Pump-Out (S1 dip switch 3 & 4)
- 4. Pump-Out Frequency Control (S1 dip switch 5 & 6)
- 5. Harvest Pump Time Duration (Harvest Assist) (S1 dip switch 7 & 8)
- 6. Freeze Timer (S1 dip switch 9 & 10)
- 7. Pump-Out/Drain Selector (S2 dip switch 1)
- 8. Harvest Promotion Control (S2 dip switch 2)
- 9. Minimum Harvest Time (S2 dip switch 3)
- 10. Harvest Completion Detection Control (S2 dip switch 4)
- 11. Overfreeze Detection Control (S2 dip switch 5)
- 12. Slush Control (S2 dip switch 6)
- IV. Refrigeration Circuit and Component Service Information
- V. Maintenance
- VI. Preparing the Appliance for Periods of Non-Use
- VII. Disposal
- VIII. Technical Information
21
C. Control Board Check
Before replacing CB that does not show a visible defect and that you suspect is bad,
always conduct the following check procedure. This procedure will help you verify your
diagnosis.
Alarm Reset: If CB is in alarm (beeping), press the "ALARM RESET" button on CB
while CB is beeping. WARNING!Risk of electric shock. Care should be
taken not to touch live terminals. Once reset, the icemaker starts at the
1-minute ll cycle. For audible alarm information, see "III.B. LED Lights and
Audible Alarm Safeties."
1) Check the dip switch settings to assure that S1 dip switch 3, 4, 7, 8, 9, 10 and S2 dip
switch 1 through 6 are in the factory default position. S1 dip switch 1, 2, 5,6 are
cleaning adjustments and the settings are exible. For factory default settings, see
"III.C.1. Default Dip Switch Settings."
2) Move the control switch to the "ICE" position. If the red CB "POWER OK" LED is on,
control voltage is good, continue to step 3. If CB "POWER OK" LED is off, check CT
secondary circuit. CT output is 10.5VAC at 115VAC primary input. If the secondary
circuit has proper voltage and the red LED is off, replace CB.
If the secondary circuit does not have proper voltage, check CT primary circuit. Check
for 115VAC at CB K3 connector pin #1 (P) to neutral (W) for 115VAC. Always choose a
white (W) neutral wire to establish a good neutral connection when checking voltages.
For additional checks, see "II.H.1. No Ice Production."
3) The "OUTPUT TEST" button provides a relay sequence test. Make sure the control
switch is in the "ICE" position, then press the "OUTPUT TEST" button. For the correct
lighting sequence, see the table below. Note that the order of the LEDs from the outer
edge of the control board is 5, 6, 8, 9, 4 and 7. Components (e.g., compressor) cycle
during the test.
Following the test, the icemaker begins operation at the 1-minute ll cycle. If the LEDs
do not light as described above, replace CB.
4) With the icemaker in the cycle to be tested, check output voltage from the corresponding
pin on CB connectors to a neutral (W)wire. If output voltage is not found and the
appropriate LED is on, replace CB.
Legend: CB–control board; CT–control transformer