Service Manual
Table Of Contents
- Important Safety Information
- I. Construction and Water/Refrigeration Circuit Diagram
- II. Sequence of Operation and Service Diagnosis
- III. Controls and Adjustments
- A. Control Board Layout
- B. LED Lights and Audible Alarm Safeties
- C. Settings and Adjustments
- 1. Default Dip Switch Settings
- 2. Harvest Time (S4 dip switch 1 & 2)
- 3. Pump-Out Time/Harvest Time During Pump-Out (S4 dip switch 3 & 4)
- 4. Pump-Out Frequency Control (S4 dip switch 5)
- 5. Harvest Pump Time (Harvest Assist) (S4 dip switch 6)
- 6. Harvest Pump Time (Harvest Assist)/Freeze-Time Correction (S4 dip switch 7)
- 7. Factory Use (S4 dip switch 8)
- 8. Freeze Timer (S4 dip switch 9 & 10)
- 9. Float Switch Selector (S5 dip switch 1)
- 10. Refill Counter (S5 dip switch 2 and 3)
- IV. Refrigeration Circuit and Component Service Information
- V. Maintenance
- VI. Preparing the Icemaker for Periods of Non-Use
- VII. Disposal
- VIII. Technical Information
- A. Specification and Performance Data
- 1. KM-1301SAJ
- 2. KM-1301SAJ3
- 3. KM-1301SWJ
- 4. KM-1301SWJ3
- 5. KM-1301SRJ with URC-14F
- 6. KM-1301SRJ3 with URC-14F
- 7. KM-1601SAJ
- 8. KM-1601SAJ3
- 9. KM-1601SWJ
- 10. KM-1601SWJ3
- 11. KM-1601SRJ with URC-22F
- 12. KM-1601SRJ3 with URC-22F
- 13. KM-1900SAJ
- 14. KM-1900SAJ3
- 15. KM-1900SWJ
- 16. KM-1900SWJ3
- 17. KM-1900SRJ with URC-22F
- 18. KM-1900SRJ3 with URC-22F
- 19. KM-2200SWJ3
- 20. KM-2200SRJ3 with URC-22F
- 21. KM-2600SWJ3
- 22. KM-2600SRJ3 with URC-26F
- B. Wiring Diagrams
- A. Specification and Performance Data
26
C. Freeze-Time Correction Cycle (90 min.)
Freeze-Time Correction function is enabled when S4 Dip Switch 7 is in the "ON" position
and initiates when the minimum and maximum freeze times have exceeded differential
parameters. Freeze-time correction timer and count starts at the beginning of the 2nd
freeze cycle after startup from power off condition. Freeze-time correction timer and count
continues and retains its freeze-time correction timer and count during a BC off cycle
and resumes its freeze-time correction timer and count on the 2nd freeze cycle after BC
restart. If freeze-time differential is exceeded (see table below), freeze-time correction
cycle starts and CB red "POWER OK" LED blinks. When freeze-time correction cycle
occurs 3 or more times within a 36 hour period, CB yellow "EXT HARVEST" LED blinks
with CB red "POWER OK" LED. Appliance starts in freeze cycle after a freeze-time
correction cycle. Toreset CB LEDs, press ALARM RESET button on CB with power on.
CB resets LEDs and appliance continues cycle without interruption.
1) Freeze Time Differential Initiation: CB starts monitoring freeze times on the second
freeze time. After 3freeze cycles (4th total), CBbegins to compare minimum and
maximum freeze time cycles. Every freeze cycle time after the rst freeze cycle
time is added to the freeze time list. Minimum and maximum freeze time differential
comparisons begin on the third cycle and are monitored up to 10cycles. On the 11th
cycle the rst freeze cycle time is dropped to maintain the 10 maximum number of
cycles.
Example: After 8 cycles (excluding rst cycle), if the differential between the
shortestcycle (minimum) and the longets cycle (maximum) is equal to or greater than
427 sec. a freeze-time correction cycle is initiated:
Number of
Freeze Cycles
Differential
Value in Sec.
3 254
4 309
5 349
6 380
7 406
8 427
9 446
10 462