Service Manual
Table Of Contents
- Important Safety Information
- I. Construction and Water/Refrigeration Circuit Diagram
- II. Sequence of Operation and Service Diagnosis
- III. Controls and Adjustments
- A. Control Board Layout
- B. LED Lights and Audible Alarm Safeties
- C. Settings and Adjustments
- 1. Default Dip Switch Settings
- 2. Harvest Timer (S4 dip switch 1 & 2)
- 3. Pump-Out Timer/Harvest Time During Pump-Out (S4 dip switch 3 & 4)
- 4. Pump-Out Frequency Control (S4 dip switch 5)
- 5. Harvest Pump Time (Harvest Assist) (S4 dip switch 6)
- 6. Harvest Pump Time (Harvest Assist)/Freeze-Time Correction (S4 dip switch 7)
- 7. Factory Use (S4 dip switch 8)
- 8. Freeze Timer (S4 dip switch 9 & 10)
- 9. Float Switch Selector (S5 dip switch 1)
- 10. Refill Counter (S5 dip switch 2 and 3)
- 11. Minimum Harvest Time (S5 dip switch 4)
- 12. Anti-Slush (S5 dip switch 5)
- D. Control Switch
- IV. Refrigeration Circuit and Component Service Information
- V. Maintenance
- VI. Preparing the Appliance for Periods of Non-Use
- VII. Disposal
- VIII. Technical Information
26
E. Bin Control Check
BC shuts down the icemaker within 10 sec. when ice contacts the thermostatic bulb,
regardless of the cycle at activation.
NOTICE
When the ambient temperature is below 45°F (7°C), BC opens and shuts down
the appliance even if the ice storage bin is empty. When BC is set in the prohibited
range, the appliance operates continuously even if the ice storage bin is lled with
ice. Setting in the prohibited range may result in severe damage to the appliance.
BC is factory set, and generally no adjustment is required. However, adjustment may be
needed in some conditions, particularly at higher altitude locations.
Note: A jumper (4A4883G01) must be placed on CB red K4connector. Otherwise,
CByellow "BC OPEN" LED is on and appliance will not start.
To check BC, follow the steps below.
1) Turn off the power supply.
2) Remove the front panel, then move the control switch to the "OFF" position.
3) Remove the control box cover and base cover, then clear any ice away from BC bulb.
4) Disconnect BC wires from BC switch.
5) Hold your hand around the bulb to warm it up.
6) Check for continuity across BC switch. If closed, continue to step 6. If open, adjust or
replace BC.
7) With the multimeter test leads still in place, hold ice on BC bulb to lower the
temperature. Within 10 sec., BC switch should open. If it remains closed, adjust or
replace BC.
Legend: BC–thermostatic bin control