Service Manual
Table Of Contents
- Important Safety Information
- I. Construction and Water/Refrigeration Circuit Diagram
- II. Sequence of Operation and Service Diagnosis
- III. Controls and Adjustments
- A. Control Board Layout
- B. LED Lights and Audible Alarm Safeties
- C. Settings and Adjustments
- 1. Default Dip Switch Settings
- 2. Harvest Time (S4 dip switch 1 & 2)
- 3. Pump-Out Time/Harvest Time During Pump-Out (S4 dip switch 3 & 4)
- 4. Pump-Out Frequency Control (S4 dip switch 5)
- 5. Harvest Pump Time (Harvest Assist) (S4 dip switch 6)
- 6. Harvest Pump Time (Harvest Assist)/Freeze-Time Correction (S4 dip switch 7)
- 7. Factory Use (S4 dip switch 8)
- 8. Freeze Timer (S4 dip switch 9 & 10)
- 9. Float Switch Selector (S5 dip switch 1)
- 10. Refill Counter (S5 dip switch 2 and 3)
- IV. Refrigeration Circuit and Component Service Information
- V. Maintenance
- VI. Preparing the Icemaker for Periods of Non-Use
- VII. Disposal
- VIII. Technical Information
- A. Specification and Performance Data
- 1. KM-1301SAJ
- 2. KM-1301SAJ3
- 3. KM-1301SWJ
- 4. KM-1301SWJ3
- 5. KM-1301SRJ with URC-14F
- 6. KM-1301SRJ3 with URC-14F
- 7. KM-1601SAJ
- 8. KM-1601SAJ3
- 9. KM-1601SWJ
- 10. KM-1601SWJ3
- 11. KM-1601SRJ with URC-22F
- 12. KM-1601SRJ3 with URC-22F
- 13. KM-1900SAJ
- 14. KM-1900SAJ3
- 15. KM-1900SWJ
- 16. KM-1900SWJ3
- 17. KM-1900SRJ with URC-22F
- 18. KM-1900SRJ3 with URC-22F
- 19. KM-2200SWJ3
- 20. KM-2200SRJ3 with URC-22F
- 21. KM-2600SWJ3
- 22. KM-2600SRJ3 with URC-26F
- B. Wiring Diagrams
- A. Specification and Performance Data
33
G. Thermistor Check
To check thermistor resistance, follow the steps below.
1) Turn off the power supply.
2) Remove the front panel. Move the control switch to the "OFF" position.
3) Remove the control box cover.
4) Remove the thermistor from the refrigerant tubing.
5) Immerse the thermistor sensor portion in a glass containing ice and water for 2 or 3 min.
6) Disconnect the thermistor connector from CB K3 connector and check the resistance
between thermistor leads. Normal range is 4.7 to 6.2 kΩ. If outside the normal range,
replace the thermistor. See "IV.B. Component Service Information." If within the normal
range, continue to the next step.
7) Replace the thermistor in its correct position. See "IV.B. Component Service
Information."
8) Reconnect the thermistor connector to CB K3 connector.
9) Replace the control box cover in its correct position.
10) Move the control switch to the "ICE" position.
11) Replace the front panel in its correct position.
12) Turn on the power supply.
13) Once the harvest cycle starts (Comp energizes), begin timing the harvest cycle.
14) The harvest timer and harvest cycle should terminate within 2 to 5 min. If the harvest
cycle does not terminate within 2 to 5 min., replace CB.
Legend: CB–control board; Comp–compressor
Foam Insulation Thermistor Holder
Thermistor Lead Cable Tie
Fig. 5
H. Control Switch
The control switch has three positions: "OFF" for power off, "ICE" for icemaking, and
"WASH" to energize the pump motor when cleaning and sanitizing. WARNING! Control
switch in "OFF" position does not de-energize all loads. Risk of electric shock.
Use extreme caution and exercise safe electrical practices.