Service Manual
Table Of Contents
- Important Safety Information
- I. Construction and Water/Refrigeration Circuit Diagram
- II. Sequence of Operation and Service Diagnosis
- III. Controls and Adjustments
- A. Control Board
- B. Controls and Adjustments
- 1. Default Dip Switch Settings
- 2. BC1 (Infrared Sensor) Shutdown Delay (S1 dip switch 1, 2, 3)
- 3. Drain Frequency Control (S1 dip switch 4)
- 4. Continuous Dispensing Timer (S1 dip switch 5 & 6)
- 5. Bin Control Selector (S1 dip switch 7)
- 6. BC2 (Mechanical Backup) Shutdown Delay (S1 dip switch 8)
- 7. Shutdown Sequence (S1 Dip Switch 9)
- 8. Alarm Selection (S1 Dip Switch 10)
- IV. Refrigeration Circuit and Component Service Information
- V. Maintenance
- VI. Disposal
- VII. Technical Information
16
6) Startup – CB "POWER OK" LED is on. Plug the icemaker back into the electrical
outlet, then move the power switch to the "ON" position. Move the control switch to the
"ICE" position. CB "POWER OK" LED and IS (BC1) green LED turn on.
Diagnosis CB "POWER OK" LED: If CB"POWER OK" LED is off, check for proper
supply voltage (115VAC) input to CT. If 115VAC is not present, check the power switch
and breaker. Next, check for proper 24VAC output voltage from CT. Check CBK8
#1 (W/R) to #2 (LBU) for 24VAC. If 24VAC is not present and 1A 24VAC fuse is
good, replace CT. If 24VAC is present and CB "POWER OK" LED is off, replace CB.
Diagnosis BC1 (infrared sensor): Check that BC1 green LED is on. If CB "POWER
OK" LED is on and BC1 green LED is off, check CB K6 #1 (DBU) to CB K6 #3 (BR)
for 20VDC. If20VDC is not present, conrm S1 dip switch 7 is in the "ON" position.
IfS1dip switch 7 is in the "ON" position and 20VDC is not present, replace CB.
IfBC1 yellow LED is on or ashing, move ice away from lens. If no ice is present, clean
the lens with a warm, clean damp cloth. If BC1 yellow LED is still on or ashing after
cleaning the lens, replace BC1.
Diagnosis BC2 (mechanical backup): CB 9-beep alarm sounds. Conrm spout cover
is properly aligned and secure. Check continuity across BC2. If open, replace BC2.
Next, check 0VDC at CB K8#3(GY) to CB K8 #4 (GY). When BC2is closed 0VDC is
read. Remove spout spring, then open the spout cover slightly to engage BC2. When
open, 5VDCis present between CB K8 #3 (GY) and CB K8#4(GY). If 5VDC is not
present when BC2 is open, replace CB. Close the spout cover and replace the spout
spring.
7) Fill Cycle – "WTRIN" LED is on. Reservoir is empty and LFS and UFS are open.
90-sec. FTstarts. WV energizes and ll cycle starts. LFS closes. Nothing occurs at this
time. Reservoir continues to ll until UFS closes. When UFS closes, FT terminates,
WV de-energizes, 90-sec. FT is terminated, and CB "WTRIN" LED turns off. 30-min.
FZTand 30-sec. GM delay timer start. IfUFS remains open longer than 90 sec. after
LFS opens, FTexceeded and CB sounds a 1-beep alarm. WVremains energized until
UFS closes. Alarm resets automatically when UFS closes.
Diagnosis: If reservoir is empty and "WTRIN" LED is off, conrm LFS status. See
"II.F.1. Float Switch Check."
If LFS is open and "WTRIN" LED is off, replace CB. If"WTRIN" LED is on, check
that the reservoir lls. If not, check water supply line shut-off valve, water lters, and
WVscreen. If "WTRIN" LED is on and WV is off, check CB K2 #8(O) to a neutral
(LBU) for 24VAC. If 24VAC is not present, check CB K2#9(W/R) to a neutral (LBU) for
24VAC. If 24VAC is present on CB K2 #9(W/R)and not on CB K2 #8 (O), replace CB.
If 24VAC is present on CB K2 #8(O), check continuity through WV solenoid. If open,
replace WV. If WV is energized and rell exceeds FT with no water in the reservoir,
check for DV leaking. Ifreservoir is full and overowing check for open UFS.
See "II.F.1. Float Switch Check." If UFS is closed, check that WV de-energizes.
If not, check CB K2 #8 (O) to a neutral (LBU) for 24VAC. If 24VAC is present, replace
CB. IfWV de-energizes and water continues to ll the reservoir, replace WV.