10) Rell Cycle – "GM", "COMP", and "WTRIN" LEDs are on.
LFS opens. WVenergizes and FT starts. GM, CCR, EH, PDS, MC, Comp, and FMR
continue. LFS closes. Nothing happens at this time. Reservoir continues to ll until UFS
closes. When UFS closes, WV de-energizes, FT terminates, and FZT starts. IfUFS
remains open longer than 90 sec. after LFS opens, FT exceeded and CB sounds a
1-beep alarm. WVremains energized until UFS closes. Alarm resets automatically when
UFS closes.
Diagnosis – Conrm that the water level has dropped and the UFS and LFS are open.
See "II.F.1. Float Switch Check." Check that "WTRIN" LED is on. IfLFS is open and
"WTRIN" LED is off, replace CB. If "WTRIN" LED is on, check that the reservoir lls.
Ifnot, check water supply line shut-off valve, water lters, and WVscreen. If"WTRIN"
LED is on and WV is off, check CB K2 #8(O) to a neutral (LBU) for 24VAC. If 24VAC is
not present, check CB K2 #9(W/R) to a neutral (LBU) for 24VAC. If 24VAC is present
on CB K2 #9 (W/R)and not on CB K2#8 (O), replace CB. If 24VAC is present on
CB K2#8(O),check continuity through WV solenoid. If open, replace WV. If WV is
energized and rell exceeds FT with no water in the reservoir, check for DV leaking. If
reservoir is full and overowing check for open UFS. See "II.F. Float Switch Check and
Cleaning." If UFS is closed, check that WVdeenergizes. If not, check CB K2 #8 (O)
to a neutral (LBU) for 24VAC. If 24VAC is present, replace CB. If WV de-energizes and
water continues to ll the reservoir, replace WV.
FT: 90-Sec. Low Water Safety TimerWhen LFS opens, 90-sec. low water safety
timer starts. If UFS does not close within 90 sec. after LFS opens (FTexceeded),
CBsounds a 1-beep alarm and a 90-sec. shutdown cycle starts.
See "III.A.2.LED Lights and Audible Alarm Safeties." PDS de-energizes. Refrigeration
circuit low-side pressure drops to 9PSIG, opening CLPS. CLPS opens, de-energizing
MC, which de-energizes Comp and FMR. GM, CCR, and EH continue. 90-sec. purge
timer terminates, GM, EH, and CCR de-energize. WV and 1-beep alarm continue until
UFS closes.