5. Bin Control Selector (S1 dip switch 7)
The bin control is factory set. No adjustment required. WARNING! Do not place
S1 dip switch 7 in the "OFF" position on dispenser unit applications. This could
lead to icemaker movement or ice overow.
S1 Dip Switch
Setting
Bin Control Application Gear Motor Delay
No. 7
OFF BC2 (mechanical stand-alone) (Standard Ice Storage Bins Only) 5 seconds
ON
BC1 (infrared sensor) Stand-Alone and
BC1 (infrared sensor) with BC2 (mechanical backup)
30 seconds
6. BC2 (Mech. Stand-Alone) Shutdown Initiation Delay (S1 dip switch 8)
Only available when S1 dip switch 7 is in the "OFF" position. Factory set for normal
operation. No adjustment is required. The shutdown initiation delay is the time between
the mechanical bin control opening and dip switch 9 timer starting.
S1 Dip Switch
Setting
Shutdown Delay
No. 8
OFF 0.25 Seconds
ON 6.7 Seconds
7. BC2 (Mech. Stand-Alone) Shutdown Time (S1 Dip Switch 9)
Only available when S1 dip switch 7 is in the "OFF" position. Factory set for optimum
performance. Do not adjust. Dip switch 9 shutdown timing starts when Dip Switch 8 timer
terminates.
S1 Dip Switch
Setting
Shutdown Sequence
No. 9
OFF
Slow timing (90s after dip switch 8 timer terminates, the COMP shuts down; 60 sec.
later, the GM shuts down)
ON
Fast timing (immediate)(after dip switch 8 timer terminates, both COMP & GM shuts
down at the same time)
8. Factory Use (S1 Dip Switch 10)
Factory set for optimum performance. Do not adjust.