10) Rell Cycle – "GM", "COMP", and "WTRIN" LEDs are on.
LFS opens. WVenergizes and 90-sec. FT starts. Comp, GM, CCR, and FM continue.
LFS closes. Nothing occurs at this time. Reservoir continues to ll until UFS closes.
When UFS closes, WV de-energizes, 90-sec. FT terminates, and 30-min. FZT starts.
IfUFS remains open longer than 90 sec. after LFS opens, FT exceeded and CB sounds
a 1-beep alarm. WVremains energized until UFS closes. Alarm resets automatically
when UFS closes.
Diagnosis – Conrm that the water level has dropped and the UFS and LFS are open.
See "II.E. Float Switch Check and Cleaning." Check that "WTRIN" LED is on. IfLFS
is open and "WTRIN" LED is off, replace CB. If "WTRIN" LED is on, check that the
reservoir lls. Ifnot, check water supply line shut-off valve, water lters, and WVscreen.
If"WTRIN" LED is on and WV is off, check CB K2 #8(O) to a neutral (LBU) for 24VAC.
If 24VAC is not present, check CB K2 #9(W/R) to a neutral (LBU) for 24VAC. If 24VAC
is present on CB K2 #9 (W/R)and not on CB K2#8 (O), replace CB. If 24VAC is
present on CB K2#8(O),check continuity through WV solenoid. If open, replace WV.
IfWV is energized and rell exceeds FT with no water in the reservoir, check for DV
leaking. Ifreservoir is full and overowing check for open UFS. See "II.E. Float Switch
Check and Cleaning." If UFS is closed, check that WVdeenergizes. If not, check
CB K2 #8(O) to a neutral (LBU) for 24VAC. If 24VAC is present, replace CB. If WV
de-energizes and water continues to ll the reservoir, replace WV.
Note: Each time UFS closes, 30-min. freeze timer starts. The 30-min. freeze timer
resets when UFS closes again. If UFS does not close again within 30 min., CB
shuts down the unit and sounds a 5-beep alarm every 5 sec.
See "III.A.2 LED Lights and Audible Alarm Safeties."
FT: 90-Sec. Low Water Safety TimerWhen LFS opens, 90-sec. low water safety
timer starts. If UFS does not close within 90 sec. after LFS opens (FTexceeded),
CBsounds a 1-beep alarm and a 90-sec. shutdown cycle starts
See "III.A.2.LED Lights and Audible Alarm Safeties." Comp and FM de-energize. GM
and CCR continue. 90-sec. purge timer terminates, GM and CCR de-energize. WV and
1-beep alarm continue until UFS closes.