4. Defrost Termination
10) Check that the components restart after defrost termination.
Refrigerator:
a) Auxiliary Code F-6 and Earlier: DTh reaches 40°F (4.4°C) Comp and ConFM
(CMC1 (R or V)) energize. If not, check DTh status. See "II.D.Thermistor Check."
IfDTh ohm reading is in proper range, and components do not energize, check for
115VAC at CM C1 (R or V) to neutral (W). If 115VAC is not present, replace CM.
If115VAC is present, check component continuity and replace as needed.
b) Auxiliary Code F-7 and Later: DTh reaches 44°F (6.6°C), Comp and ConFM (CM
C1 (V)), and EvapFM (CM F5 (W/BU)) energize. If not, check DTh status. See
"II.D.Thermistor Check." If DTh ohm reading is in proper range, and components
do not energize, check for 115VAC at CM C1 (V) and CM F5 (W/BU) to neutral
(W). If 115VAC is not present, replace CM. If 115VAC is present, check component
continuity and replace as needed.
Freezer:
a) Auxiliary Code F-7 and Earlier: DTh reaches 59°F (15°C) or 45°F (7.2°C). 3-min.
later, Comp and ConFM (CM C1 (RorV)) and EvapFM (CM F5 (Y or W/BU))
energize. If not, check DTh status. See "II.D.Thermistor Check." IfDTh ohm reading
is in proper range, and Comp, ConFM, or EvapFM do not energize, replaceCM.
12min. after Comp, ConFM, and EvapFM energize, cabinet temperature appears on
CM. If components fail to start, check continuity, replace as needed.
b) Auxiliary Code F-8 and Later: DTh reaches 45°F (7.2°C). 3-min. later, Comp and
ConFM (CM C1 (V)) and EvapFM (CM F5 (W/BU)) energize. If not, check DTh status.
See "II.D.Thermistor Check." IfDTh ohm reading is in proper range, and Comp and
ConFM (CM C1 (V)), or EvapFM (CM F5 (W/BU)) do not energize, replaceCM.
12min. after Comp, ConFM, and EvapFM energize, cabinet temperature appears on
CM. If components fail to start, check continuity, replace as needed.
Legend: CM–control module; Comp–compressor; ConFM–condenser fan motor;
CTh–cabinet thermistor; DH–defrost heater; DS–door switch; DTh–defrost
thermistor; EvapFM–evaporator fan motors, MH–mullion heater; PH–perimeter
heater