Service Guide
31
2b) Manually-Initiated Defrost-Termination: Has DTh warmed to 45°F (7.2°C)?
Ifnot, conrm DTh status. See "II.D. Thermistor Check." If DTh is in proper range,
DHde-energizes and 2 delay timers start. If DTh has not warmed to 45°F (7.2°C),
check DT and DH continuity. Next, check DH amp draw.
(1) 3-min. Comp and EvapFM delay timers terminate: 3 min. after DH
de-energizes, conrm defrost icon turns off, Comp and EvapFM icons turn on,
and Comp, ConFM, EvapFM, MH, and PH energize. If not, conrm cabinet
temperature is warm enough for Comp and ConFM operation.
CM and Defrost Thermistor Diagnosis: Check for 115VAC at CM C1 (V) to
neutral(W). If115VAC is not present, check CTh status. See "II.D.Thermistor
Check." If CTh ohm reading is in proper range, replace CM.
MH and PH Diagnosis: Check for 115VAC at CR 0 (P and O) to neutral (W).
If 115VAC is not present, check HPS continuity. See "f) HPS Activation" above.
Comp and ConFM: Check for 115VAC at CR 0 (P and O) to neutral (W).
If115VAC is not present, check HPS continuity. See "f) HPS Activation" above.
If 115VAC is present, check for 115VAC at CR #4(BK) to neutral (W) and
CR#6(R) to neutral (W). If 115VAC is present at CR #4 (BK) to neutral (W) but
not at CR #6(R) to neutral (W), replace CR. If 115VAC is present at CR #6 (R)
and Comp or ConFM are not energized, check Comp start components, Comp
protector (internal on 1-section, external on 2-section), and Comp motor winding
continuity. If ConFM is not energized, check ConFM fan blades for binding and
motor winding continuity.
EvapFM: Conrm EvapFM icon turns on and EvapFM energizes. If not, conrm
doors are closed and DS engaged. Next, check for 115VAC at CMF5 (W/
BU) to neutral (W). If 115VAC is not present, replace CM. If 115VAC is present,
checkfor 115VAC at DSR#4(DBU) to neutral(W). If115VAC is not present,
check for 115VAC at DSR#6(W/BU) to neutral (W). If115VAC is present on
DSR #6(W/BU) to neutral (W) and not on DSR #4(DBU) to neutral (W), replace
DSR. If 115VAC is present on DSR #4 (DBU) to neutral (W) and EvapFM is not
energized, check EvapFM blades for binding and EvapFM continuity.
(2) 15-min. temperature display delay timer terminates: 12 min. after Comp,
ConFM, and EvapFM energize, "dEF" is replaced by cabinet temperature on
display. If not, replace CM.
Legend: CL–cabinet light; CLS–cabinet light switch; CM–control module;
Comp–compressor; ConFM–condenser fan motor; CR–compressor relay;
CTh–cabinet thermistor; DCD–direct current driver; DH–defrost heater; DrH–drain
heater; DSR–door switch relay; DT–defrost thermostat; DTh–defrost thermistor;
EvapFM–evaporator fan motors; HPS–high-pressure switch; MH–mullion heater;
PH–perimeter heater; TXV–thermostatic expansion valve