(4) EvapFM Diagnosis: Conrm EvapFM de-energizes. If not, check for 115VAC at
DSR 4 (DBU) to neutral (W). If 115VAC is present, replace DSR.
2a) Time-Initiated Defrost-Termination: DTh warmes to 45°F (7.2°C). Ifnot, conrm
DTh status. See "II.D. Thermistor Check." IfDTh is in proper range, DHde-energizes
and 3 delay timers start. If DTh has not warmed to 45°F (7.2°C), check DT and DH
continuity. Next, check DH amp draw.
(1) 3-min. Comp delay timer terminates: 3 min. after DH de-energizes, conrm
defrost icon turns off, Comp icon turns on, and Comp, ConFM, MH, and
PH energize. If not, conrm cabinet temperature is warm enough for Comp
operation. Next, check for 115VAC at CM C1 (V) to neutral(W). If115VAC is not
present, check CTh status. See "II.D.Thermistor Check." If CTh ohm reading is in
proper range, replace CM. If 115VAC is present:
MH and PH Diagnosis: If MH and PH are de-energized, check for 115VAC at
CR 0 (P and O). If 115VAC is present at CM C1 (V) to neutral (W) and not at CR
0 (P and O), check HPS continuity. See "f) HPS Activation" above.
Comp and ConFM Diagnosis: Check for 115VAC at CR 0 (P and O). If 115VAC
is present at CM C1 (V) to neutral (W) and not at CR 0 (P and O), check HPS
continuity. See "f) HPS Activation" above. If 115VAC is present at CR 0 (P and
O) to neutral (W), check for 115VAC at CR#4(BK) to neutral (W) and CR#6(R)
to neutral (W). If 115VAC is present at CR #4 (BK) to neutral (W) but not at CR
#6(R) to neutral (W), replace CR. If115VAC is present at CR #6 (R) and Comp
or ConFM are not energized, check Comp start components, Comp protector
(internal on 1-section, external on 2-section), and Comp motor winding continuity.
If ConFM is not energized, check ConFM fan blades for binding and motor
winding continuity.
(2) 7-min. EvapFM delay timer terminates: (note that the 7-min. EvapFM delay time
is a maximum; if the defrost thermistor cools to 25°F (-3.9°C) before the 7-min.
EvapFM delay timer terminates, EvapFM icon turns on and EvapFM energizes):
4min. after Comp energizes, conrm EvapFM icon turns on and EvapFM
energizes. If not, conrm doors are closed and DS engaged. Next, check for
115VAC at CMF5 (W/BU) to neutral (W). If 115VAC is not present, replace
CM. If 115VAC is present, checkfor 115VAC at DSR#4(DBU) to neutral(W).
If115VAC is not present, check for 115VAC at DSR#6(Y or W/BU) to neutral
(W). If115VAC is present on DSR #6 (W/BU) to neutral (W) and not on DSR
#4(DBU) to neutral (W), replace DSR. If 115VAC is present on DSR #4 (DBU) to
neutral (W) and EvapFM is not energized, check EvapFM blades for binding and
EvapFM continuity.
(3) 18-min. temperature display delay timer terminates: 11 min. after EvapFM
energizes, "dEF" is replaced by cabinet temperature on display. If not, replace
CM.