Service Guide
30
(4) EvapFM Diagnosis: Conrm EvapFM de-energizes. If not, check for 115VAC at
DSR 4 (DBU) to neutral (W). If 115VAC is present, replace DSR.
2a) Time-Initiated Defrost-Termination: DTh warmes to 45°F (7.2°C). Ifnot, conrm
DTh status. See "II.D. Thermistor Check." IfDTh is in proper range, DHde-energizes
and 3 delay timers start. If DTh has not warmed to 45°F (7.2°C), check DT and DH
continuity. Next, check DH amp draw.
(1) 3-min. Comp delay timer terminates: 3 min. after DH de-energizes, conrm
defrost icon turns off, Comp icon turns on, and Comp, ConFM, MH, and
PH energize. If not, conrm cabinet temperature is warm enough for Comp
operation. Next, check for 115VAC at CM C1 (V) to neutral(W). If115VAC is not
present, check CTh status. See "II.D.Thermistor Check." If CTh ohm reading is in
proper range, replace CM. If 115VAC is present:
MH and PH Diagnosis: If MH and PH are de-energized, check for 115VAC at
CR 0 (P and O). If 115VAC is present at CM C1 (V) to neutral (W) and not at CR
0 (P and O), check HPS continuity. See "f) HPS Activation" above.
Comp and ConFM Diagnosis: Check for 115VAC at CR 0 (P and O). If 115VAC
is present at CM C1 (V) to neutral (W) and not at CR 0 (P and O), check HPS
continuity. See "f) HPS Activation" above. If 115VAC is present at CR 0 (P and
O) to neutral (W), check for 115VAC at CR#4(BK) to neutral (W) and CR#6(R)
to neutral (W). If 115VAC is present at CR #4 (BK) to neutral (W) but not at CR
#6(R) to neutral (W), replace CR. If115VAC is present at CR #6 (R) and Comp
or ConFM are not energized, check Comp start components, Comp protector
(internal on 1-section, external on 2-section), and Comp motor winding continuity.
If ConFM is not energized, check ConFM fan blades for binding and motor
winding continuity.
(2) 7-min. EvapFM delay timer terminates: (note that the 7-min. EvapFM delay time
is a maximum; if the defrost thermistor cools to 25°F (-3.9°C) before the 7-min.
EvapFM delay timer terminates, EvapFM icon turns on and EvapFM energizes):
4min. after Comp energizes, conrm EvapFM icon turns on and EvapFM
energizes. If not, conrm doors are closed and DS engaged. Next, check for
115VAC at CMF5 (W/BU) to neutral (W). If 115VAC is not present, replace
CM. If 115VAC is present, checkfor 115VAC at DSR#4(DBU) to neutral(W).
If115VAC is not present, check for 115VAC at DSR#6(Y or W/BU) to neutral
(W). If115VAC is present on DSR #6 (W/BU) to neutral (W) and not on DSR
#4(DBU) to neutral (W), replace DSR. If 115VAC is present on DSR #4 (DBU) to
neutral (W) and EvapFM is not energized, check EvapFM blades for binding and
EvapFM continuity.
(3) 18-min. temperature display delay timer terminates: 11 min. after EvapFM
energizes, "dEF" is replaced by cabinet temperature on display. If not, replace
CM.