Service Guide
27
2b. Freezer: Auxiliary Code F-8 and Later
7) Startup/Cool Down–Lights and DrH energize. There is a slight delay, then Comp,
ConFM, EvapFM, MH, and PH energize. Cabinet temperature appears on display and
5-hr.Comp cumulative run time defrost timer starts.
a) Cabinet Light FGE (FGECR & FGECL) Diagnosis: Open the door conrm CLS is in
the ON position. If not, move CLS to the ON position.
LEDs turn on. If LEDs do not turn on, check for 115VAC at CLS yellow (Y) wire
to neutral(W) and CLS black (BK) wire to neutral (W). If 115VAC is present at
CLSyellow (Y) wire and not at CLS black (BK) wire, conrm continuity of CLS switch.
IfCLS is engaged and CLS switch is open, replace CLS. IfCLS is engaged, contacts
are closed, and 115VAC is present at CLSblack (BK) wire to neutral (W) and LEDs
are not on, check for 24VDC at DCD output black (BK) wire to DCD output red (R)
wire. If 24VDC is not present, check continuity of DCD driver. If open, replace DCD
driver. If 24VDC is present and LEDs are not on, check wire harness and wiring
connections from DCD to LED. If connections are good and LEDs are not on, replace
LED.
FS/HS CL Diagnosis: Open the door (upper on HS) and conrm CL is energized.
Ifnot, with the door open, check for 115VAC at DSR #5 (BK) to neutral(W) and DSR
#1 (Y) to neutral(W). If115VAC is not present at DSR #5 (BK), conrm power supply
and continuity of power switch. If 115VAC is present at DSR #5 (BK) and not present
at DSR #1 (Y), check DS continuity. IfDS is disengaged and contacts are closed
(DSR energized), replace DS. If DSR is de-energized and 115VAC is present at
DSR#5(BK) and not at DSR #1 (Y) to neutral (W), replace DSR.
If 115VAC is present at DSR #1 (Y) and CL is not energized, replace CL.
b) DrH Diagnosis: Conrm amp draw of DrH. If no amp draw available, check for
115VAC to DrH black wire (BK) to neutral (W). If 115VAC is present, check DrH
continuity. If open, replace DrH. If 115VAC is not present, check wiring connections to
DrH.
c) CM Diagnosis: Cabinet temperature appears on display. If not, check for 115VAC
at CM L2 (BK) to CM N3 neutral (W). If 115VAC is not present, conrm wiring
connections are secure on CM L2 (BK) (power supply) and CM N3 (W) (neutral).
If115VAC is present and display is off, replace CM.
d) Comp and ConFM Diagnosis: Conrm Comp and ConFM energize. If not, check for
115VAC at CM C1 (V) to neutral (W). If 115VAC is not present, check CTh status. See
"II.D.Thermistor Check." If CTh ohm reading is in proper range, replace CM. If not in
range, replace thermistor. If115VAC is present at CM C1 (V) to neutral (W), check
for 115VAC at CR #0 (P) to CR #1 (W). If 115VAC is not present, check continuity
of HPS. Ifopen, allow time for HPS to reset (cut out: 490 ±10 PSIG, cut in: 370 ±20
PSIG). If HPS does not reset, see "g) HPS Activation" below. If HPS is closed and
115VAC is present, check for 115VAC at CR #4 (BK) and CR #6 (R) to neutral (W).
If115VAC is present at CR #4 (BK) and not at CR #6(R), replace CR. If115VAC is
present at CR #6 (R) to neutral (W) and ConFM is energized but Comp is not: On
1-section; Give time for internal protector to cool and reset. Next, check run capacitor,
start capacitor, start relay, and Comp motor windings. If Comp does not start, replace
Comp. On 2-section; Check for 115VAC at Comp external protector to neutral (W).
If 115VAC is not present, give time for Comp external protector to cool and reset.