Service Guide
13
2a. Freezer: Auxiliary Code F-7 and Earlier
Freezer Auxiliary Code F-7 and Earlier Sequence Flow Chart
3. Cool Down Restart
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermistor
DH-defrost heater
DrH-drain heater
DTh-defrost thermistor
EvapFM-evaporator fan motor
MH-mullion heater
PH-perimeter heater
1. Startup/Cool Down
2. Cool Down Achieved
Comp energized
ConFM energized
EvapFM energized
MH energized
PH energized
CTh in control
Slight
Delay at
Startup
CTh cools to
3°F (1.7°C)
below setpoint.
Factory default
-4°F (-20°C)
CTh warms
to 3°F (1.7°C)
above setpoint
4. Defrost
EvapFM energized
MH energized
PH energized
Comp de-energized
ConFM de-energized
5. Defrost Termination
MH energized
PH energized
DH de-energized
DrH de-energized
After Delay:
Comp energized
ConFM energized
EvapFM energized
DTh warms to 59°F (15°C)
Note:
a) EvapFM de-energizes when door is opened on -FS models and when upper door is opened on -HS models.
b) 2-min. minimum Comp on timer starts when Comp energizes.
c) 2-min. minimum Comp off timer starts when Comp de-energizes.
d) 5-min. minimum defrost time.
e) 1-hr. maximum defrost time.
f) 3-min. Comp/ConFM delay timer starts when defrost termination temperature is met.
g) 7-minute EvapFM delay timer starts when defrost termination temperature is met (3-minute delay timer when defrost initiated manually)
h) 18-minute temperature display delay timer starts when defrost termination temperature is met (15-minute delay timer when defrost
initiated manually).
DTh in control
Power on
DH energized
DrH energized
MH energized
PH energized
Comp de-energized
ConFM de-energized
EvapFM de-energized
2-min. Comp off
timer starts
MH energized
PH energized
2-min. Comp on
timer starts
4-hr. cumulative Comp run
time defrost timer starts
4-hr cumulative Comp run
time defrost timer terminates