Service Manual

10
1. Startup/Cool Down
3. Cool Down Restart
Cycle Steps
Slight
Delay at
Startup
Power On
CTh in control
3-min. Comp on
timer starts
EvapFM energized Comp energized
ConFM energized
EvapFM de-energized
Comp de-energized
ConFM de-energized
EvapFM de-energized
Comp de-energized
ConFM de-energized
EvapFM de-energized
Comp energized
ConFM energized
EvapFM energized
2. Cool Down Achieved
3-min. Comp off
timer starts
CTh warms
to 10°F (-12°C)
above setpoint
5. Defrost Termination
DTH warms to
55°F (13°C) or
25 mins
maximum
defrost timer
terminates
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermistor
DTh-defrost thermistor
EvapFM-evaporator fan motor
Note:
a) EvapFM de-energizes when door is opened on.
b) 3-min. minimum Comp on timer starts when Comp energizes.
c) 3-min. minimum Comp off timer starts when Comp de-energizes.
d) 25-min. maximum defrost time.
e) Setpoint temperature is displayed during defrost.
4. Defrost
8 hrs Interval between defrosts
25-min.
maximum
defrost
DTH in
control
Setpoint factory
default :
-8°F (-22°C)
2. Freezer