Service Manual
Table Of Contents
- Important Safety Information
- I. Construction and Water Refrigeration Circuit Diagrams
- II. Sequence of Operation and Service Diagnosis
- III. Controls and Adjustments
- A. Control Board Layout
- B. LED Lights and Audible Alarm Safeties
- C. Settings and Adjustments
- 1. Default Dip Switch Settings
- 2. Bin Control Shutdown Delay (Infrared Sensor) (S1 dip switch 1, 2, 3)
- 3. Drain Frequency Control (S1 dip switch 4)
- 4. Continuous Dispensing Timer (S1 dip switch 5 & 6)
- 5. Bin Control Selector (S1 dip switch 7)
- 7. Bin Control Shutdown Delay (S1 dip switch 9) (F-C CB Only)
- 8. Factory Use (S1 Dip Switch 10)
- D. Switches
- IV. Refrigeration Circuit and Component Service Information
- V. Maintenance
- VI. Preparing the Appliance for Periods of Non-Use
- VII. Disposal
- VIII. Technical Information
24
13) a. "F-A" CB E-0 (G) and Earlier Dip Switch 8 "ON": Comp and GM should
de-energize within 10seconds.
b. "F-A" CB E-0 (H) and Later Dip Switch 8 "OFF": 90-sec. Comp shutdown timer
starts. Once 90-sec. Comp shutdown timer terminates, Comp and FM de-energize
and 60-sec. GM shutdown timer starts. Once 60-sec. GM shutdown timer terminates,
GM de-energizes.
c. "F-C" CB dip switch 8 and 9 "OFF": 90-sec. Comp shutdown timer starts. Once
90-sec. Comp shutdown timer terminates, Comp and FM de-energize and 60-sec.
GM shutdown timer starts. Once 60-sec. GM shutdown timer terminates, GM
de-energizes.
Diagnosis: If BC micro-switch is found open and the appliance continues to run,
replace CB.
14) Move the power switch to the "OFF" position. Leave the control switch in the "ICE"
position.
15) Replace the storage bin cover and secure.
16) Replace the control box cover, left side, top, and front panels in their correct positions.
17) Move the power switch to the "ON" position to start the automatic icemaking process.
Legend: BC–bin control; CB–control board; Comp–compressor; FM–fan motor;
GM–gear motor