Service Manual
Table Of Contents
- Important Safety Information
- I. Construction and Refrigeration Circuit Diagram
- II. Sequence of Operation and Service Diagnosis
- III. Controls and Adjustments
- IV. Refrigeration Circuit and Component Service Information
- V. Maintenance
- VI. Preparing the Appliance for Periods of Non-Use
- VII. Disposal
- VIII. Technical Information
- A. Electrical and Refrigerant Data
- B. Wiring Diagrams
- 1a. Refrigerator: Undercounter and Worktop Auxiliary Code C-5(D) and Earlier
- 1b. Refrigerator: Undercounter and Worktop Auxiliary Code C-5(E) and Later
- 2a. Refrigerator: Prep Table Auxiliary Code C-5(D) and Earlier
- 2b. Refrigerator: Prep Table Auxiliary Code C-5(E) and Later
- 3a. Freezer: All Auxiliary Code C-5(D) and Earlier
- 3b. Freezer: All Auxiliary Code C-5(E) and Later
12
2. Refrigerator: Prep Table
Refrigerator: Prep Table Sequence Flow Chart
2. Cool Down
3. Cool Down Achieved
CTh closed
Comp energized
ConFM energized
EvapFM energized
CTh open
EvapFM energized
Comp de-energized
ConFM de-energized
4. Defrost
8-hr. DT terminates
20-min. DT starts
EvapFM energized
Comp de-energized
ConFM de-energized
20-min. DT terminates
8-hr. DT starts
Legend: Comp–compressor; ConFM–condenser fan motor; CTh–cabinetthermostat;
8-hr. DT–8-hour defrost timer; 20-min.DT–20-minutedefrosttimer;
EvapFM–evaporatorfanmotor
CTh above setpoint
CTh cools to setpoint
CTh above
setpoint
CTh above
setpoint
20 min. DT in control
CTh in control
1. Startup
EvapFM energized
Freezer Sequence Flow Chart
1. Startup/Cool Down
2. Cool Down Achieved
CTh closed
Comp energized
ConFM energized
EvapFM energized
MH energized
PH energized
CTh open
Comp de-energized
ConFM de-energized
EvapFM de-energized
MH de-energized
PH de-energized
3. Defrost
8-hr. DT terminates
20-min. DT starts
DH energized
Comp de-energized
ConFM de-energized
EvapFM de-energized
MH de-energized
PH de-energized
3. Freezer: All
Legend: Comp–compressor; ConFM–condenser fan motor; CTh–cabinetthermostat;
DH–defrostheater; 8-hr. DT–8-hour defrost timer;
20-min.DT–20-minutedefrosttimer; EvapFM–evaporatorfanmotor;
MH–mullionheater; PH–perimeterheater
20-min. DT terminates
8-hr. DT starts
DH de-energized
CTh in control
CTh above setpoint
CTh cools to setpoint
CTh above
setpoint
CTh above
setpoint
20 min. DT in control