The first five System Diagnostics are critical. If any of them indicate a Fault condition, the XLe/XLt will not
enter or remain in Run mode, and the problem must be investigated and corrected. 
System Ram:  Ok  = System RAM power-up self-test passed 
  Fault  = System RAM power-up self-test failed 
System BIOS:  Ok  = System BIOS power-up self-test passed 
  Fault  = System BIOS power-up self-test failed 
Firmware:  Ok  = Firmware power-up self-test passed 
  Fault  = Firmware power-up self-test failed 
Logic Error:  Ok  = All executed ladder instructions are legal for loaded firmware 
  Fault  = A ladder instruction not
 supported by firmware was found 
User Program:  Ok  = Ladder program and I/O configuration loaded successfully 
  Fault  = Ladder program or I/O configuration not loaded or load failed 
The last nine System Diagnostics are informational. If any of them indicate a Warning condition, the 
XLe/XLt can still enter and remain in Run mode, but the problem should be investigated and corrected. 
User Graphics: Ok = Application graphics objects loaded successfully 
  Fault  = Application graphics objects not loaded or load failed 
W-Dog Trips:  0  = Watchdog timer has not tripped since the last power-up 
  x  = Number of times watchdog timer has tripped 
Net Errors:  0  = No CAN network bus-off errors have occurred 
  x  = Number of CAN network bus-off errors that have occurred 
Network State:  Ok  = At least one other node was found on the CAN network 
  Warning  = No other nodes were found on the CAN network 
Network ID:  Ok  = This node’s CAN Network ID is in the range 1 to 253 
  Warning  = This node’s CAN Network ID was out of range at power-up 
Dup Net ID:  Ok  = This node’s Network ID is unique on the CAN network 
  Warning  = This node’s Network ID is duplicated in another node 
Clock Error:  Ok  = Time and date have been set 
  Warning  = Time and date need to be set 
I/O System:  Ok  = I/O configuration matches the installed I/O and COM modules 
  Warning  = I/O configuration needs updating to match installed modules 
Battery:  Ok  = Backup battery operating properly 
  Warning  = Backup battery needs to be replaced 