4 Serial Communications
5 Wiring and Jumpers
Wire according to the type of inputs / outputs used, and select the appropriate
jumper option.
5.1. Wiring Examples
J1 Orange
Terminal
Connector
XE102
Name
I1 IN1
I2 IN2
I3 IN3
I4 IN4
I5 IN5
I6 IN6
I7 IN7
I8 IN8
H1 HSC1 /IN9
0V Ground
A1 ES2T-250/300
A2 ESP-100
A3 Analog IN3
A4 Analog IN4
0V Ground
5.2. I/O Jumpers Settings (JP1 - JP2)
5.3. External DIP Switch Settings (or Jumpers Settings)
6 Derating
J2 Black
Terminal
Connector
XE102
Name
C6 Relay 6 COM
R6 Relay 6 NO
C5 Relay 5 COM
R5 Relay 5 NO
C4 Relay 4 COM
R4 Relay 4 NO
C3 Relay 3 COM
R3 Relay 3 NO
C2 Relay 2 COM
R2 Relay 2 NO
C1 Relay 1 COM
R1 Relay 1 NO
H4 HSC4 / IN12
H3 HSC3 / IN11
H2 HSC2 / IN10
Serial Communications:
MJ1: (RS-232 / RS-485) Use for Cscape programming and Application-
Defined Communications.
MJ2: (RS-232 / RS-485) Use for Application-Defined Communications.
Pin
MJ1 Pins MJ2 Pins
Signal Direction Signal Direction
8 TXD OUT TXD OUT
7 RXD IN RXD IN
6 0 V Ground 0 V Ground
5 NC
No
Connect
NC
No
Connect
4 RTS OUT TX- OUT
3 CTS IN TX+ OUT
2
RX- /
TX-
IN / OUT RX- IN
1
RX+ /
TX+
IN / OUT RX+ IN
1
8
001XLE015
0V ON J1
12-24VDC
R2
C2
R3
C3
R6
C6
R4
C4
R5
C5
R1
C1
H4
H2
H3
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
XE102 J2 Black
Positive Logic
Digital In / Relay Out
Location of I/O jumpers (JP
)
and wiring connectors
(J1 and J2).
I1
0V
001XLE036
12-24VDC
I1
0V
Positive Logic In Negative Logic In
Positive Logic vs. Negative Logic Wiring
The XLE can be wired for Positive Logic inputs or Negative
Logic inputs.
Wiring Specifications
For I/O wiring (discrete), use the
following wire type or equivalent:
Belden 9918, 18 AWG or larger.
For shielded Analog I/O wiring,
use the following wire type or
equivalent: Belden 8441, 18
AWG or larger.
For CAN wiring, use the
following wire
type or equivalent:
Belden 3084, 24 AWG or larger.
J1
JP2
JP1
J2
001XLE062
Note:
Loop Power requirements are determined
by the transmitter specification.
Note: The Cscape Module Setup configuration must match the selected I/O (JP) jumper settings.
001XLE026
JP1 Digital DC In / HSC
Positive Negative
Logic Logic
Default
JP2 Analog In (A3 – A4)
Current Voltage
(20 mA) (10 V)
Note:
When using JP2 (A3-A4),
each channel can be
independently configured.
001XLE066
Some XLes have jumpers
to set RS-485 port
termination, though most
use DIP Switches.
The External Jumpers or
DIP Switches are used for
termination of the RS-485
ports. The XLE is shipped
un-terminated.
To terminate, select one
of the jumpers shipped
with the product and
insert it based upon the
option that is desired or,
select the switch and
configure based upon the
option that is desired.
Factory Use
(default – none)
MJ2 Termination
(default – none)
MJ1 T
ermination
(default – none)
001XLE037
As seen when looking at the top of the XLE unit: Refer to
Section 3 for the location of the External Jumpers.
001XLE037-R1
Factory Use
(default – none)
MJ2 Termination
(default – none)
MJ1 Termination
(default – none)
XLE102 Relay Life Expectancy
0
10
20
30
40
1 2 3 4
Contact Current (A)
Operation
(x10
4
)
12-24VDC
I1
I2
I3
I4
0V
A1
A2
0V
I5
I6
I7
I8
A3
A4
H1
001XLE067
20mA LOOP
0-10VDC
P
T
XE102 J1 Orange
Positive Logic in
Digital In / Analog In