Self-Test: Ok = All power-on self-tests passed
Fault = One or more power-on self-tests failed
View Diags
The View Diags Sub-Menu displays up to 14 System Diagnostics, none of which are editable.
The first two System Diagnostics are critical. If any of them indicate a Fault condition, the XL6/XL6e OCS
will not
enter or remain in Run mode, and the problem must be investigated and corrected.
Logic Error: Ok = All executed ladder instructions are legal for loaded firmware
Fault = A ladder instruction not
supported by firmware was found
User Program: Ok = Ladder program and I/O configuration loaded successfully
Fault = Ladder program or I/O configuration not loaded or load failed
The last nine System Diagnostics are informational. If any of them indicate a Warning condition, the
XL6/XL6e OCS can still enter and remain in Run mode, but the problem should be investigated and
corrected.
User Graphics: Ok = Application graphics objects loaded successfully
Fault = Application graphics objects not loaded or load failed
W-Dog Trips: 0 = Watchdog timer has not tripped since the last power-up
x = Number of times watchdog timer has tripped
Net Errors: 0 = No CAN network bus-off errors have occurred
x = Number of CAN network bus-off errors that have occurred
Network State: Ok = At least one other node was found on the CAN network
Warning = No other nodes were found on the CAN network
Network ID: Ok = This node’s CAN Network ID is in the range 1 to 253
Warning = This node’s CAN Network ID was out of range at power-up
Dup Net ID: Ok = This node’s Network ID is unique on the CAN network
Warning = This node’s Network ID is duplicated in another node
Clock Error: Ok = Time and date have been set
Warning = Time and date need to be set
I/O System: Ok = I/O configuration matches the installed I/O and COM modules
Warning = I/O configuration needs updating to match installed modules