Owner's manual

MAN0902-01-EN Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________
3/26/2009 Page 5 of 7 ECN # 956
4.5 Power Port and Wiring
5 Wiring and Jumpers
Wire according to the type of inputs / outputs used, and select the
appropriate jumper option.
5.1 I/O Jumpers Settings (JP1)
5.2 Wiring Examples
J1 Orange
Terminal
Connector
Name
I1 IN1
I2 IN2
I3 IN3
I4 IN4
I5 IN5
I6 IN6
I7 IN7
I8 IN8
H1 HSC1 /IN9
0V Ground
A1 Thermistor 1
A2 Thermistor 2
A3 Thermistor 3
A4 Thermistor 4
0V Ground
J2 Black
Terminal
Connector
Name
C6 Relay 6 COM
R6 Relay 6 NO
C5 Relay 5 COM
R5 Relay 5 NO
C4 Relay 4 COM
R4 Relay 4 NO
C3 Relay 3 COM
R3 Relay 3 NO
C2 Relay 2 COM
R2 Relay 2 NO
C1 Relay 1 COM
R1 Relay 1 NO
H4 HSC4 / IN12
H3 HSC3 / IN11
H2 HSC2 / IN10
6 Analog Conditioning
6.1 Filter
Filter Constant sets the level of digital filtering according to the following chart.
Digital Filtering. The illustration above demonstrates the effect of digital filtering (set with Filter Constant)
on module response to a temperature change.
It is recommended that the filter constant for the HE-XL102-14/HE-XL1E2-14 be set to a value of 7. This
will minimize noise and jitter, improve effective resolution, and provide adequate speed for most
temperature monitor and control applications.
Primary Power Port Pins
Pin Signal Description
1 Ground Frame Ground
2 V- Input Power Supply Ground
3 V+ Input Power Supply Voltage
I1
0V
001XLE036
12-24VDC
I1
0V
Positive Logic In Negative Logic In
Positive Logic vs. Negative Logic Wiring
The XL6 HEXL102
can be wired for Positive Logic
inputs or Negative Logic inputs.
001XLE015
0V ON J1
12-24VDC
R2
C2
R3
C3
R6
C6
R4
C4
R5
C5
R1
C1
H4
H2
H3
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
230VAC
OR
25VDC
N
L
230VAC
OR
25VDC
N
L
230VAC
OR
25VDC
N
L
230VAC
OR
25VDC
N
L
J2 Black
Positive Logic
Digital In / Relay Out
Wiring Specifications
For I/O wiring (discrete), use the following wire type or
equivalent: Belden 9918, 18 AWG (0.8 mm
2
) or larger.
For shielded Analog I/O wiring, use the following wire type or
equivalent: Belden 8441, 18 AWG (0.8 mm
2
) or larger.
For CAN
wiring, use the following wire type or equivalent:
Belden 3084, 24 AWG (0.2 mm
2
) or larger.
Use copper conductors in field wiring only, 60/75° C
J1
JP2
JP1
J2
001XLE025
60
20
100
40
80
20
0
10
100
90
80
70
60
50
40
30
Scans
0
1 2 3 4 5
6
0 7
%
C
o
m
p
l
e
t
e
[
]
Filter
Constant
Location of I/O jumpers (JP2 and JP1) and wiring
connectors
(J1 and J2).
Note:
The Cscape Module Setup configuration must match the selected
I/O (JP) jumper settings.
JP1 Digital DC In / HSC
Positive Negative
Logic Logic
Default
Power Connector
Power Up:
Connect to Earth Ground.
Apply 10 - 30 VDC.
Screen lights up.
Torque rating 4.5 – 7 Lb-In
(0.50 – 0.78 N-m)
J1 Orange
Positive Logic In
Digital In /
Analog In
I1
I2
I3
I4
0V
A1
A2
0V
I5
I6
I7
I8
A3
A4
H1
001XLE067
12-24VDC
T
T
T
T