Manual

MAN0964-01-EN CH.12
June 29, 2012 Page 63 of 122
User Program: Ok = Ladder program and I/O configuration loaded successfully
Fault = Ladder program or I/O configuration not loaded or load failed
The last nine System Diagnostics are informational. If any of them indicate a Warning condition, the XL4
OCS can still enter and remain in Run mode, but the problem should be investigated and corrected.
User Graphics: Ok = Application graphics objects loaded successfully
Fault = Application graphics objects not loaded or load failed
W-Dog Trips: 0 = Watchdog timer has not tripped since the last power-up
x = Number of times watchdog timer has tripped
Net Errors: 0 = No CAN network bus-off errors have occurred
x = Number of CAN network bus-off errors that have occurred
Network State: Ok = At least one other node was found on the CAN network
Warning = No other nodes were found on the CAN network
Network ID: Ok = This node’s CAN Network ID is in the range 1 to 253
Warning = This node’s CAN Network ID was out of range at power-up
Dup Net ID: Ok = This node’s Network ID is unique on the CAN network
Warning = This node’s Network ID is duplicated in another node
Clock Error: Ok = Time and date have been set
Warning = Time and date need to be set
I/O System: Ok = I/O configuration matches the installed I/O and COM modules
Warning = I/O configuration needs updating to match installed modules
Battery: Ok = Backup battery operating properly
Warning = Backup battery needs to be replaced
View I/O Slots
The View I/O Slots Sub-Menu displays three System Settings, all of which are not editable.
Internal to the XL4 OCS, there is a CPU board, and up to two installed modules. Model XE100 has no
installed I/O or COM modules. All other models have an I/O module and can have a user-installed COM
module.
Depending on which I/O module is installed and which I/O module has been configured by Cscape, one
of the following six System Settings should appear for Slot 1: