User Manual
SUP0740-07 CH.1
11/30/2009 Page 9 of 98 # 958
1.3 Ethernet System Requirements and Interoperability
Full Ethernet functionality requires:
¾ PC running Cscape Programming Software Version 7.0c or later (for configuration)
¾ OCS controller with built-in or user-installed Ethernet Module (ETN200 / ETN300)
¾ FTP & HTTP protocols supported only
by OCS Models with built-in Ethernet and
Compact Flash/Micro SD.
The server protocols, supported by the ETN200 / ETN300 have been tested for interoperability
with Cscape and several 3
rd
party client software packages (Table 1.3).
Table 1.3 – Ethernet Module Server Protocol Interoperability
Client Software Package Ethernet Module Server Protocol
Name Version CsCAN SRTP Modbus EIP FTP HTTP
Cscape Programming
Software
7.0c
√
GE Proficy View * 5.50.3655
√
GE Fanuc Cimplicity HMI 3.2
√
5.0
√
GE Fanuc Cimplicity PE
6.1
√ √
KEPware OPC / DDE
Server
4.84.227
√ √
Pyramid EIP Scanner
Demo
3.51
√
5.50.4522
√ √
Microsoft Internet Explorer
6.0.2900
√ √
SmartFTP 1.5.990
√
Mozilla Firefox 1.0.7
√
* When selecting the PLC Access Driver for SRTP mode using Proficy View software, be sure to
select GE Fanuc TCP/IP.
1.4 Ethernet Module Specifications
Table 1.4 – Specifications
General
Ethernet Speeds
10 BaseT Ethernet (10 Mbps)
100 BaseTx Fast Ethernet (100 Mbps)
Ethernet Modes Half or Full Duplex
Ethernet Auto-Negotiation Both 10 / 100 Mbps and Half / Full Duplex
Ethernet Connector Type Shielded RJ-45
Ethernet Cable Type Recommendation CAT5 (or better) UTP
Ethernet Port (Applicable to QX351and XL6e) Auto MDI/MDI-X
Application Protocols
ICMP Ping Only
CsCAN TCP Server Maximum Connections = 8
EGD (Ethernet Global Data)
Maximum Exchanges = 127
Maximum Data Bytes per Exchange = 1,400
SRTP Server Maximum Connections = 16
Modbus TCP Slave Maximum Connections = 16
Ethernet / IP Server Maximum Connections = 2
FTP Server Maximum Connections = 4