User Manual
OCX003  19 MAR 2003  PAGE 5 
Information is subject to change without notice. Cscape is a trademark of Horner APG, LLC. 
4  CONFIGURATION 
Note: The status of the I/O can be monitored in Cscape Software. 
Digital Filtering. The illustration above demonstrates the effect of digital filtering (set with Fillter 
Constant) on module response to a temperature change. 
Module Setup Tab 
The Module Setup is used to configure the Analog 
Inputs and Analog Outputs ±10V and ±20mA modes 
and for applications where it is necessary to change the 
default states or values of the outputs when the 
controller (e.g., OCS100) enters idle/stop mode. 
1. For Digital Outputs: The default turns the outputs 
OFF when the controller enters idle/stop mode. By 
selecting the Module Setup tab, each output can be set 
to either turn ON, turn OFF or to hold the last state. 
Generally, most applications use the default settings. 
Warning: The default turns the digital outputs OFF 
when the controller enters idle/stop mode. To avoid 
injury of personnel or damages to equipment, 
exercise extreme caution when changing the default 
settings. 
2. For Analog Inputs 
Mod
e: ±10V or ±20mA must be set for each channel. The 
associated slide switch on the back of the module must 
match the Cscape setting for each channel. 
Filter Constant: Sets the level of digital filtering according 
to the following chart. 
I/O Map Tab 
The I/O Map describes which I/O registers are assigned. 
The I/O Map is not edited by the user. 