User Manual
PAGE 58  15 MAR 2003  CH.6 
    MAN0305-02 
6.7  SmartStix I/O Module Consumed (Received) Directed Data  
Table 6.4 – Consumed Directed Data Word 1 
16-bit Word 
8-bit High Byte  8-bit Low Byte 
Digital Output Control Data – Low Word 
Q16  Q15  Q14  Q13  Q12  Q11  Q10  Q9  Q8  Q7  Q6  Q5  Q4  Q3  Q2  Q1 
Q16…Q1  Controls the Off / On state of the SmartStix I/O Module’s 1st 16 Digital Outputs, if any. 
Table 6.5 – Consumed Directed Data Word 2 
16-bit Word 
8-bit High Byte  8-bit Low Byte 
Digital Output Control Data - High Word 
Q32  Q31  Q30  Q29  Q28  Q27  Q26  Q25  Q24  Q23  Q22  Q21  Q20  Q19  Q18  Q17 
Q32…Q17 Controls the Off / On state of the SmartStix I/O Module’s 2nd 16 Digital Outputs, if any. 
Table 6.6 – Consumed Directed Data Word 3 
16-bit Word 
8-bit High Byte  8-bit Low Byte 
Diagnostic Command Data  Configuration Command Data 
Reserved for Future Products            CIT 
CH
T 
CL
T 
CLT = 0  Command the SmartStix I/O Module to set its Life Expectancy Time to 2.0 seconds, as the maximum 
time to wait between Control Station to SmartStix I/O Module output control data messages, before 
setting all Digital Outputs to their default states. 
CLT = 1  Command the SmartStix I/O Module to use Word 4’s Life Expectancy Time. In this case, a value of 0.0 
disables the Life Expectancy feature. 
CHT = 0  Command the SmartStix I/O Module to set its Heartbeat Send Time to 1.0 second, as the minimum time 
between SmartStix I/O Module to Control Station Heartbeat messages. 
CHT = 1  Command the SmartStix I/O Module to use Word 4’s Heartbeat Send Time. In this case, a value of 0.0 
disables the Heartbeat Send feature. 
CIT = 0   Command the SmartStix I/O Module to send its Digital Input data to the Control Station, only when the 
Digital Inputs change state. 
CIT = 1   Command the SmartStix I/O Module to use Word 4’s Digital Input Send Time, to determine how often to 
periodically send its Digital Input data to the Control Station.  In this case, a value of 0.0 disables 
automatic sending of Digital Input data. 
  Note:  Regardless of the CIT setting, Digital Inputs are always sent to the Control Station when the 
SmartStix I/O Module powers -up, and when specifically requested by the Control Station. 
Table 6.7 – Consumed Directed Data Word 4 
16-bit Word 
8-bit High Byte  8-bit Low Byte 
Digital Input / Heartbeat Send Time Data  Life Expectancy Time Data 
0.0 to 25.5 seconds = Minimum Send Interval  0.0 to 25.5 seconds = Maximum Receive Interval 
See Directed Data Word 3’s CLT, CHT and CIT command descriptions above.