PAGE 58 15 MAR 2003 CH.6
MAN0305-02
6.7 SmartStix I/O Module Consumed (Received) Directed Data
Table 6.4 Consumed Directed Data Word 1
16-bit Word
8-bit High Byte 8-bit Low Byte
Digital Output Control Data Low Word
Q16 Q15 Q14 Q13 Q12 Q11 Q10 Q9 Q8 Q7 Q6 Q5 Q4 Q3 Q2 Q1
Q16…Q1 Controls the Off / On state of the SmartStix I/O Module’s 1st 16 Digital Outputs, if any.
Table 6.5 Consumed Directed Data Word 2
16-bit Word
8-bit High Byte 8-bit Low Byte
Digital Output Control Data - High Word
Q32 Q31 Q30 Q29 Q28 Q27 Q26 Q25 Q24 Q23 Q22 Q21 Q20 Q19 Q18 Q17
Q32…Q17 Controls the Off / On state of the SmartStix I/O Module’s 2nd 16 Digital Outputs, if any.
Table 6.6 Consumed Directed Data Word 3
16-bit Word
8-bit High Byte 8-bit Low Byte
Diagnostic Command Data Configuration Command Data
Reserved for Future Products CIT
CH
T
CL
T
CLT = 0 Command the SmartStix I/O Module to set its Life Expectancy Time to 2.0 seconds, as the maximum
time to wait between Control Station to SmartStix I/O Module output control data messages, before
setting all Digital Outputs to their default states.
CLT = 1 Command the SmartStix I/O Module to use Word 4’s Life Expectancy Time. In this case, a value of 0.0
disables the Life Expectancy feature.
CHT = 0 Command the SmartStix I/O Module to set its Heartbeat Send Time to 1.0 second, as the minimum time
between SmartStix I/O Module to Control Station Heartbeat messages.
CHT = 1 Command the SmartStix I/O Module to use Word 4’s Heartbeat Send Time. In this case, a value of 0.0
disables the Heartbeat Send feature.
CIT = 0 Command the SmartStix I/O Module to send its Digital Input data to the Control Station, only when the
Digital Inputs change state.
CIT = 1 Command the SmartStix I/O Module to use Word 4’s Digital Input Send Time, to determine how often to
periodically send its Digital Input data to the Control Station. In this case, a value of 0.0 disables
automatic sending of Digital Input data.
Note: Regardless of the CIT setting, Digital Inputs are always sent to the Control Station when the
SmartStix I/O Module powers -up, and when specifically requested by the Control Station.
Table 6.7 Consumed Directed Data Word 4
16-bit Word
8-bit High Byte 8-bit Low Byte
Digital Input / Heartbeat Send Time Data Life Expectancy Time Data
0.0 to 25.5 seconds = Minimum Send Interval 0.0 to 25.5 seconds = Maximum Receive Interval
See Directed Data Word 3’s CLT, CHT and CIT command descriptions above.