2.2  MiniRCS Mounting Requirements 
2.2.1  MiniRCS Mounting Procedures (Installed in a Panel Box) 
The MiniRCS is designed for permanent installation in a panel box. To install the MiniRCS in a panel 
box, use the instructions that follow:  
1. Prior to mounting the MiniRCS, observe requirements for the panel layout design and adequate 
clearances. A checklist is provided on page 25.  
2. Drill holes as described in the Figure 2.9.  
3. Install and tighten washers and nuts. Do not over-tighten. 
4. Connect the communications and power cables to the MiniRCS ports using the provided connectors. 
5. Begin configuration procedures for the MiniRCS models.  
2.2.2   MiniRCS Dimensions and Panel Cut-outs 
Figure 2.9 – MiniRCS Dimensions / Mounting Holes and MiniRCS Side View 
Warning: Make sure the power and network connectors are removed from the MiniRCS. 
001RCS001
0.91 [23.19mm] 4.00 [101.60mm]
0.19
[4.78mm]
3.75
(95.25mm)
4.13
(104.78mm)
5.83 [147.98mm]
1.83 [46.48mm]
MOUNTING HOLES FOR
#6 OR M3.5 HARDWARE
4 PLCS.