Instruction Manual

PAGE 6 15 JAN 2010 MAN0432-04
Table 5
– LED Description
LED RCS
RUN
OFF indicates OCS is in IDLE/STOP mode.
Flashing at 1 Hz indicates DO / IO mode or RUN with no ladder program.
ON indicates ladder code running.
OK
OFF indicates one or more self-tests failed.
Flashing at 1 Hz indicates I/O forcing is active.
ON indicates all self-tests passed.
Module Status (MS)
MS monitors RS-232 activity
OFF indicates no RS-232 communication.
Red flickering indicates receive activity on the RS-232 port.
Green flickering indicates transmit activity on the RS-232 port.
Orange flickering indicates both transmit and receive activity on the RS-
232 port.
Red solid ON indicates a non-critical self-test error was detected
Red flashing at 1Hz indicates a critical self-test error was detected.
Network Status (NS)
NS monitors CAN port
activity
OFF indicates no CAN communication.
Red flickering indicates receive activity on the CAN port.
Green flickering indicates transmit activity on the CAN port.
Orange flickering indicates both transmit and receive activity on the CAN
port.
Red solid ON indicates a CAN network error was detected.
4 SAFETY
All applicable codes and standards need to be followed in the installation of this product.
5 TECHNICAL ASSISTANCE
For updates and assistance, contact Technical Support at the following locations.
North America:
(317) 916-4274
www.heapg.com
Europe:
(+) 353-21-4321-266
www.horner-apg.com