Spec Sheet

Table Of Contents
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—07 60
10130 Ventilation Low
Temperature
Lockout
Off
-20° F to 40° F (in 5° F
increments)
Off Both No Requires an outdoor sensor.
This ISU is only displayed when ISU 10000
Ventilation Type is set to ERV / HRV or Fresh Air
Damper.
See “Ventilation — Outdoor Condition Lockouts
(ISU 10130)” beginning on page 115.
10130 Ventilation High
Temperature
Lockout
Off
80° F to 110° F (in 5° F
increments)
Off Both No Requires an outdoor sensor.
This ISU is only displayed when ISU 10000
Ventilation Type is set to ERV / HRV or Fresh Air
Damper.
See “Ventilation — Outdoor Condition Lockouts
(ISU 10130)” beginning on page 115.
10130 Ventilation High Dew
Point Lockout
Off
65° F to 85° F (in 5° F increments)
Off Both No Requires a Wireless Outdoor Sensor (sense
outdoor humidity).
This ISU is only displayed when ISU 10000
Ventilation Type is set to ERV / HRV or Fresh Air
Damper.
See “Ventilation — Outdoor Condition Lockouts
(ISU 10130)” beginning on page 115.
10140 Lockout Ventilation
on Humidification or
Dehumidification
Calls
Off
On
Off Both No This feature is used to help reach the user's
desired humidity level by not allowing the
ventilation equipment to run during a call for
humidification or dehumidification.
Off: Ventilation is allowed to run during a call
for humidification or dehumidification.
On: Ventilation is NOT allowed to run during a
call for humidification or dehumidification.
10160 Ventilate on High
Indoor Humidity
Off
On (Heat Mode Only)
On (Heat Mode
Only)
Both No This ISU is only displayed when ISU 10000
Ventilation Type is set to ERV / HRV.
Off: The humidity level has no effect on
ventilation.
On: The thermostat removes excess humidity
by turning on the ventilator when the indoor
humidity rises 10% above the user's
humidification setting. The thermostat must be
in the heat mode to ventilate on high humidity.
10170 Ventilator Core
Cleaning Reminder
Off
3, 6, 9, 12 Calendar Months
Off Both No
10170 Ventilator Filter
Cleaning Reminder
Off
3, 6, 9, 12 Calendar Months
Off Both No
11000 Number of UV
Devices
0, 1, 2
0 Both No Press the up/down arrows to select the number
of UV devices installed in the system. Some
systems may have two UV devices, one for the
A-Coil and another for Air Treatment. A
replacement reminder can be setup for each
one. Select 0 if no UV devices are installed.
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes