THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—07 56
9070 Dehumidification -
Overcooling Limit
0°, 1°, 2°, 3° F
3° F Residential No This ISU is only displayed when ISU 9000
Dehumidification Equipment is set to A/C with
Low Speed Fan or A/C with High Speed Fan.
The thermostat uses the cooling system to
reduce humidity by lowering the temperature
up to 3° F below the current cool setpoint until
the desired humidity level is reached.
The thermostat keeps the temperature below
the cooling setpoint until the desired humidity
level is reached.
0° F is only an option when ISU 9000
Dehumidification Equipment is set to A/C with
Low Speed Fan.
9080 Dehumidification
Control
Basic
Minimum On Time
High Humidity Comfort Reset
High Humidity Comfort Reset with
Minimum On Time
Reheat
Reheat with Minimum On Time
Basic Commercial No See “Dehumidification - Commercial”
beginning on page 110.
9090 Dehumidification
Minimum On Time
5 to 15 minutes
10 minutes Commercial No This option ensures that the compressor runs
long enough to effectively reduce humidity
when the cooling equipment is cycled on. The
compressor will run for the “minimum on time”
you set until the desired humidity level is
reached.
9100 High Humidity
Comfort Reset
Setting
1° F to 5° F
2° F Commercial No The thermostat uses the cooling system to
reduce humidity by lowering the temperature
up to 5° F below the current cool setpoint until
the desired humidity level is reached.
The thermostat keeps the temperature below
the cooling setpoint until the desired humidity
level is reached.
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes