Spec Sheet

Table Of Contents
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
49 68-0311—07
6030 Remote Setback
Time Delay from
Occupied to
Unoccupied
0 to 30 minutes (in 5 minute
increments)
0 minutes Commercial Yes Remote Setback requires an EIM (Equipment
Interface Module).
The Remote Setback Time Delay forces the
thermostat to wait before it switches from
Occupied to Standby temperature settings.
When set to 0 minutes, the thermostat will
switch from Occupied to Standby temperature
settings immediately when the room is
unoccupied.
6040 Remote Setback -
Standby Cool
Setpoint
72° F to 90° F
85° F Commercial Yes Remote Setback requires an EIM (Equipment
Interface Module).
During occupied periods, the occupancy sensor
tells the thermostat to go to STANDBY (setback
settings) when no one is in the room. If
someone is in the room, then it follows the
settings of the occupied period. The occupancy
sensor is ignored during unoccupied periods.
If the thermostat is setup for non-
programmable, the occupancy sensor tells the
thermostat to go to STANDBY settings when no
one is in the room. If someone is in the room,
then it follows the settings set by the user.
6040 Remote Setback -
Standby Heat
Setpoint
50° F to 70° F
64° F Commercial Yes Remote Setback requires an EIM (Equipment
Interface Module).
During occupied periods, the occupancy sensor
tells the thermostat to go to STANDBY (setback
settings) when no one is in the room. If
someone is in the room, then it follows the
settings of the occupied period. The occupancy
sensor is ignored during unoccupied periods.
If the thermostat is setup for non-
programmable, the occupancy sensor tells the
thermostat to go to STANDBY settings when no
one is in the room. If someone is in the room,
then it follows the settings set by the user.
6050 What Terminals are
Wired to the Full
Drain Pan Alert Dry
Contact?
None
S1
S2
S3
S4
None Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
6060 Full Drain Pan Alert
Dry Contact Setup
Normally Open
Normally Closed
Normally Open Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed.
Normally Open: The Dry Contact device is
normally open and will close when the device
detects the drain pan is full.
Normally Closed: The Dry Contact device is
normally closed and will open when the device
detects the drain pan is full.
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes