4140 Residential:
Entry / Exit Remote -
Vacation Heat
Setpoint
Commercial:
Entry / Exit Remote -
Holiday Heat
Setpoint
None
40° F to 90° F
Note: setpoint is limited based on
setting at ISU 4100.
60° F Both No The thermostat maintains this Heat setting
when the user presses Vacation / Holiday at the
Entry / Exit Remote. Select None to delete this
temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See
“Wireless Entry/Exit Remote” beginning on
page 130.
5000 What Sensors are
WIRED to your
System?
Check box on screen for each:
Indoor Air Temperature
Outdoor Air Temperature
Return Air Temperature
Discharge Air Temperature
None Both Yes Wired Sensors requires an EIM (Equipment
Interface Module). This ISU is only displayed if
one of the S1-S4 terminals is available.
Click boxes on screen to select which sensors
are wired to the S1-S4 terminals at the EIM.
The thermostat will not display the Outdoor Air
Temperature option at ISU 5000 if a wireless
outdoor air sensor is connected.
The thermostat will not display the Indoor Air
Temperature option at ISU 5000 if 6 wireless
indoor air sensors are connected. If you have a
wired Indoor Air Temperature network (1, 4, 9
etc), the thermostat will allow up to 5 wireless
indoor air sensors.
The thermostat will not display the Return /
Discharge Air Temperature option at ISU 5000
if there is no fan in the system.
5010 Indoor Temperature
Sensor Name
[Sensor Name]
Indoor Sensor Both Yes Wired Sensors requires an EIM (Equipment
Interface Module).
Enter a name (location) of the Wired Indoor Air
Temperature Sensor.
5020 What Terminals are
Wired to the Indoor
Temperature Sensor?
None
S1
S2
S3
S4
None Both Yes Wired Sensors requires an EIM (Equipment
Interface Module).
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes