Spec Sheet

Table Of Contents
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
43 68-0311—07
4070 Minimum Cool
Recovery Ramp Rate
Off
1° F/hr to 20° F/hr
3° F/hr Commercial No Off: The cooling system will begin recovery at
the time that is scheduled.
When a Minimum Recovery Ramp Rate is set,
the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a Minimum Recovery Ramp Rate based on
the rate that the cooling system can recover at
for a hot day in your region. Default setting is 3°
F / hour.
If an outdoor sensor is installed, set an Outdoor
Temperature that is representative of a hot day
in your region to be associated with the
Minimum Recovery Ramp Rate. The thermostat
will begin recovery at the optimal time based on
a calculated ramp rate, allowing the system to
recover on time and save energy during
changing outdoor conditions.
During recovery, the setpoint changes at a rate
in degrees per hour depending on the outdoor
temperature. If there is no outdoor sensor, the
Minimum Recovery Ramp Rate is used.
4070 Outdoor
Temperature used
with Minimum Cool
Recovery Ramp Rate
Off
-20° F to 100° F
90° F Commercial No Off: The cooling system will begin recovery at
the time that is scheduled.
When a Minimum Recovery Ramp Rate is set,
the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a Minimum Recovery Ramp Rate based on
the rate that the cooling system can recover at
for a hot day in your region. Default setting is 3°
F / hour.
If an outdoor sensor is installed, set an Outdoor
Temperature that is representative of a hot day
in your region to be associated with the
Minimum Recovery Ramp Rate. The thermostat
will begin recovery at the optimal time based on
a calculated ramp rate, allowing the system to
recover on time and save energy during
changing outdoor conditions.
During recovery, the setpoint changes at a rate
in degrees per hour depending on the outdoor
temperature. If there is no outdoor sensor, the
Minimum Recovery Ramp Rate is used.
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes