Spec Sheet

Table Of Contents
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
41 68-0311—07
4030 Override Duration
No Limit
1 to 12 Hours
3 hours Commercial No When the user presses the OVERRIDE button,
the thermostat will maintain the new
temperature for at least 1 hour. The user can
adjust the Hold Until time from 1 hour to the
amount set for the Override Duration (1-12
hours). Default setting is 3 hours. If set to No
Limit, the user can adjust the Hold Until time
up to 24 hours.
4050 Minimum Heat
Recovery Ramp Rate
Off
1° F/hr to 20° F/hr
5° F/hr Commercial No Off: The heating system will begin recovery at
the time that is scheduled.
When a Minimum Recovery Ramp Rate is set,
the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a Minimum Recovery Ramp Rate based on
the rate that the heating system can recover at
for a cold day in your region. Default setting is
5° F / hour.
If an outdoor sensor is installed, set an Outdoor
Temperature that is representative of a cold day
in your region to be associated with the
Minimum Recovery Ramp Rate. The thermostat
will begin recovery at the optimal time based on
a calculated ramp rate, allowing the system to
recover on time and save energy during
changing outdoor conditions.
During recovery, the setpoint changes at a rate
in degrees per hour depending on the outdoor
temperature. If there is no outdoor sensor, the
Minimum Recovery Ramp Rate is used.
4050 Outdoor
Temperature used
with Minimum Heat
Recovery Ramp Rate
Off
-20° F to 100°F
0° F Commercial No Off: The heating system will begin recovery at
the time that is scheduled.
When a Minimum Recovery Ramp Rate is set,
the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a Minimum Recovery Ramp Rate based on
the rate that the heating system can recover at
for a cold day in your region. Default setting is
5° F / hour.
If an outdoor sensor is installed, set an Outdoor
Temperature that is representative of a cold day
in your region to be associated with the
Minimum Recovery Ramp Rate. The thermostat
will begin recovery at the optimal time based on
a calculated ramp rate, allowing the system to
recover on time and save energy during
changing outdoor conditions.
During recovery, the setpoint changes at a rate
in degrees per hour depending on the outdoor
temperature. If there is no outdoor sensor, the
Minimum Recovery Ramp Rate is used.
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes