Spec Sheet

Table Of Contents
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
33 68-0311—07
3060 Staging Control -
Compressor Heat
Differential Stage 1
Comfort
1.0° F to 4.0° F from setpoint (in
0.5° F increments)
Comfort Both No ISU 3010 Temperature Control Options must
be set to Advanced to view or adjust this ISU.
This ISU is only displayed if ISU 2010 Heating
Equipment Type is Geothermal Radiant Heat
and ISU 2050 Geothermal Forced Air System is
set to Used for Heating and Cooling.
The indoor temperature must drop to the
selected differential setting before the
thermostat will turn on the stage of heating. For
example, if stage 1 is set to 2° F (1.0° C), the
indoor temperature must be 2° F (1.0° C) away
from the setpoint before stage 1 turns on.
When set to Comfort, the thermostat will use
the stage of heating as needed to keep the
indoor temperature within 1° F (0.5° C) degree
of the setpoint.
3060 Staging Control -
Compressor Heat
Differential Stage 2
Comfort
1.0° F to 4.5° F from setpoint (in
0.5° F increments)
Comfort Both No ISU 3010 Temperature Control Options must
be set to Advanced to view or adjust this ISU.
This ISU is only displayed if ISU 2010 Heating
Equipment Type is Air to Air Heat Pump,
Geothermal Heat Pump or Geothermal Radiant
Heat and there are 2 compressor stages.
The indoor temperature must drop to the
selected differential setting before the
thermostat will turn on the stage of heating. For
example, if stage 2 is set to 2° F (1.0° C), the
indoor temperature must be 2° F (1.0° C) away
from the setpoint before stage 2 turns on.
When set to Comfort, the thermostat will use
the stage of heating as needed to keep the
indoor temperature within 1° F (0.5° C) degree
of the setpoint.
3080,
3090
Staging Control -
Backup Heat
Differential Stage 1
Note: “Stage 1" is not
displayed if there is
only 1 stage of
Backup Heat.
Comfort
2.0° F to 15.0° F from setpoint (in
0.5° F increments)
Comfort Both No A backup heat differential can be set on any
system that has more than one heating
equipment type.
See “Backup Heat Differential (Droop)”
beginning on page 97.
The Comfort setting is only available on
systems when the Backup Heat Type is Allowed
to Run with the Primary Heat (Heat Pump). For
example, Heat Pumps with Electric Forced Air
Backup Heat.
The Comfort setting is NOT available for Dual
Fuel systems. For example, Heat Pumps with
Gas Forced Air.
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes