Spec Sheet

Table Of Contents
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—07 32
3040 Staging Control -
Radiant Heat
Differential Stage 2
Comfort
1.0° F to 3.5° F from setpoint (in
0.5° F increments)
Comfort Both No ISU 3010 Temperature Control Options must
be set to Advanced to view or adjust this ISU.
This ISU is only displayed if ISU 2010 Heating
Equipment Type is Geothermal Radiant Heat
and there are 2 radiant heat stages.
The indoor temperature must drop to the
selected differential setting before the
thermostat will turn on the stage of heating. For
example, if stage 2 is set to 2° F (1.0° C), the
indoor temperature must be 2° F (1.0° C) away
from the setpoint before stage 2 turns on.
When set to Comfort, the thermostat will use
the stage of heating as needed to keep the
indoor temperature within 1° F (0.5° C) degree
of the setpoint.
3050 Staging Control -
Heat Differential
Stage 2
Note: Depending on
the application, the
text displayed on the
screen may show the
specific heating
equipment type
Comfort
1.0° F to 3.5° F from setpoint (in
0.5° F increments)
Comfort Both No ISU 3010 Temperature Control Options must
be set to Advanced to view or adjust this ISU.
This ISU is only displayed for conventional
systems that have 2 heat stages.
The indoor temperature must drop to the
selected differential setting before the
thermostat will turn on the stage of heating. For
example, if stage 2 is set to 2° F (1.0° C), the
indoor temperature must be 2° F (1.0° C) away
from the setpoint before stage 2 turns on.
When set to Comfort, the thermostat will use
the stage of heating as needed to keep the
indoor temperature within 1° F (0.5° C) degree
of the setpoint.
3050 Staging Control -
Heat Differential
Stage 3
Note: Depending on
the application, the
text displayed on the
screen may show the
specific heating
equipment type
Comfort
1.0° F to 4.0° F from setpoint (in
0.5° F increments)
Comfort Both No ISU 3010 Temperature Control Options must
be set to Advanced to view or adjust this ISU.
This ISU is only displayed for conventional
systems that have 3 heat stages.
The indoor temperature must drop to the
selected differential setting before the
thermostat will turn on the stage of heating. For
example, if stage 3 is set to 2° F (1.0° C), the
indoor temperature must be 2° F (1.0° C) away
from the setpoint before stage 3 turns on.
When set to Comfort, the thermostat will use
the stage of heating as needed to keep the
indoor temperature within 1° F (0.5° C) degree
of the setpoint.
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes