THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
31 68-0311—07
3021 Finish With High
Heat Stage
No
Yes
No Both No ISU 3010 Temperature Control Options must
be set to Advanced to view or adjust Finish With
High Heat Stage.
This ISU is only displayed when the thermostat
is set for 2 or more heat stages.
When set to Yes, this feature keeps the high
stage of the heating equipment running until
the desired setpoint is reached.
3030 Staging Control -
Cool Differential
Stage 2
Comfort
1.0° F to 3.5° F from setpoint (in
0.5° F increments)
Comfort Both No ISU 3010 Temperature Control Options must
be set to Advanced to view or adjust this ISU.
This ISU is only displayed when the thermostat
is set to 2 cool stages.
The indoor temperature must rise to the
selected differential setting before the
thermostat turns on the stage of cooling. For
example, if stage 2 is set to 2° F (1.0° C), the
indoor temperature must be 2° F (1.0° C) away
from the setpoint before stage 2 turns on.
When set to Comfort, the thermostat uses the
stage of cooling as needed to keep the indoor
temperature within 1° F (0.5° C) degree of the
setpoint.
3030 Staging Control -
Cool Differential
Stage 3
Comfort
1.0°F - 4.0°F from setpoint (in
0.5° F increments)
Comfort Commercial No ISU 3010 Temperature Control Options must
be set to Advanced to view or adjust this ISU.
This ISU is only displayed when the thermostat
is set to 3 cool stages.
The indoor temperature must rise to the
selected differential setting before the
thermostat turns on the stage of cooling. For
example, if stage 3 is set to 2° F (1.0° C), the
indoor temperature must be 2° F (1.0° C) away
from the setpoint before stage 3 turns on.
When set to Comfort, the thermostat uses the
stage of cooling as needed to keep the indoor
temperature within 1° F (0.5° C) degree of the
setpoint.
3030 Staging Control -
Cool Differential
Stage 4
Comfort
1.0° F to 4.5° F from setpoint (in
0.5° F increments)
Comfort Commercial No ISU 3010 Temperature Control Options must
be set to Advanced to view or adjust this ISU.
This ISU is only displayed when the thermostat
is set to 4 cool stages.
The indoor temperature must rise to the
selected differential setting before the
thermostat turns on the stage of cooling. For
example, if stage 4 is set to 2° F (1.0° C), the
indoor temperature must be 2° F (1.0° C) away
from the setpoint before stage 4 turns on.
When set to Comfort, the thermostat uses the
stage of cooling as needed to keep the indoor
temperature within 1° F (0.5° C) degree of the
setpoint.
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes