Spec Sheet

Table Of Contents
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
29 68-0311—07
2220 A-L/A Terminal
Setup
None
Time Of Day
Economizer
Heat Pump Failure Indication
None Commercial No This ISU is only displayed when ISU 1010
Application is Commercial.
Note: When the thermostat is setup for
Residential, the L/A terminal operates as
described under “Heat Pump Failure
Indication.” The L/A terminal requires no setup
for residential applications.
None: The A-L/A terminal is not used.
Time of Day: The A-L/A terminal is energized
during Occupied periods and when the user
overrides the temperature. The terminal is de-
energized during Unoccupied periods and in
Standby mode.
Economizer: The thermostat controls an
economizer module to provide ventilation
during Occupied periods and free cooling when
outdoor conditions are favorable. The A-L/A
terminal is energized during Occupied periods
and during a call for cooling in Unoccupied
periods. See “Economizer and Time of Day
(TOD) Operation” beginning on page 128.
Notes: The economizer module determines
when outdoor conditions are favorable for free
cooling. Delta T Diagnostics is not available
when the thermostat is setup for an
Economizer. If an economizer fault alert is
required, see Fig. 355 on page 156.
Heat Pump Failure Indication: When 24 volts is
detected on the L/A terminal (compressor
monitor), the thermostat displays a message to
alert the user when the heat pump requires
service. The L/A terminal sends a continuous
output to a zone panel when the thermostat is
set to Emergency Heat mode. The zone panel
will not turn on the heat pump when a zone is
set to Emergency Heat mode.
3000 Changeover
Manual
Automatic
Manual:
if ISU 1010 is
Residential
Automatic:
if ISU 1010 is
Commercial
Both No Manual: The user must select heating or
cooling as needed to maintain the desired
indoor temperature.
Automatic: The user has the option to select
Auto for the system setting. In Auto mode, the
thermostat controls heating and cooling
equipment as needed to maintain the desired
indoor temperature.
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes