Spec Sheet

Table Of Contents
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—07 100
HEAT PUMP AND BACKUP HEAT OPERATION
Heat pump with outdoor temperature lockouts
Outdoor temperature lockouts are optional. See Installer Setup options (ISU 3120).
Geothermal Radiant Heat
The thermostat can be setup to control Geothermal
Radiant Heat, Geothermal Forced Air Heat and Backup
Heat, all from one thermostat. The thermostat stages the
equipment starting with the Geothermal Radiant Heat
followed by Geothermal Forced Air Heat and then Backup
Heat as needed to maintain the desired temperature. The
thermostat allows you to set differential temperature
settings between each stage if you want the equipment to
stage a certain way (see ISU 3030 to ISU 3090, page 31).
For additional wiring diagrams, see page 144.
NOTE: To turn off Radiant Heat during the shoulder sea-
sons, install an outdoor reset control and connect
to the Radiant Heat or switch the thermostat to
Emergency Heat mode.
Electric Backup Heat (Backup Heat
Allowed to Run with Heat Pump)
HEAT MODE
The thermostat turns on Backup Heat only when the
indoor temperature drops to the selected Backup Heat
Differential setting or the Backup Heat Upstage Timer
Table 8. Heat Pump and Backup Heat Operation.
Backup Heat Type Backup Heat Operation Backup Heat Fan Operation
Electric forced air Allowed to run with heat pump Thermostat controls fan
Gas or oil forced air NOT allowed to run with heat pump Equipment controls fan
Hot water radiant heat Allowed to run with heat pump [n/a]
Hot water fan coil Selectable in installer setup Thermostat controls fan
Other Selectable in installer setup Selectable in installer setup
Heat pump only
Heat pump with backup heat as needed *
Backup heat only
Heat pump only
Heat pump or backup heat operates *
Backup heat only
Outdoor temperatureOutdoor temperature
Backup heat lockout
Backup heat lockout
Compressor lockout
Compressor lockout
* No backup heat unless indoor temperature drops to selected Backup Heat Differential setting, or Backup Heat
Upstage Timer expires. Heat pump stays ON when backup heat turns on.
* No backup heat unless indoor temperature drops to selected Backup Heat Differential setting, or Backup
Heat Upstage Timer expires. Heat pump turns OFF when backup heat turns on.
Backup heat allowed to run with heat pump (see table below)
Backup heat NOT allowed to run with heat pump (see tab
le below)