Prestige and VisionPRO EIM Spec Sheet 2013
Table Of Contents
- Application
- Features
- Contents
- Specifications
- System Installation
- Installation Options
- Guidelines for Installing RedLINK Devices
- Installing Equipment Interface Module (if used)
- Wiring 24 Vac Common
- Selecting Discharge and Return Air Temperature Sensor Mounting Locations
- Selecting Return Air Temperature Sensor Mounting Location
- Installing Discharge and Return Air Temperature Sensors
- Selecting Thermostat Location
- Installing Wallplate
- Power Optional REDLINK™ Accessories
- Performing Initial Setup
- Linking Thermostat to Equipment Interface Module (if used)
- Linking RedLINK™ Accessories
- Completing Initial Setup
- Adding RedLINK Accessories to the Thermostat
- Locating the Connect Buttons on RedLINK Accessories
- Finding Your Password (Date Code) to Access Installer Options
- Installer Options
- Making Changes to Installer Setup
- Installer Tests
- Operation
- Setting the time/date
- Setting the fan
- Setting system mode
- Preset Energy-Saving Schedules
- Adjusting program schedules
- Overriding schedules: residential use
- Overriding schedules: commercial use
- Viewing equipment status
- Setting vacation hold: residential use
- Setting holiday/event schedules: commercial use
- Setting custom events: commercial use
- Setting holiday schedule: commercial use
- Setting holiday override: commercial use
- Initiating occupancy mode: commercial use
- Remote setback: commercial use
- Adjusting humidification settings
- Adjusting dehumidification settings: residential use
- Adjusting dehumidification settings: commercial use
- Adjusting ventilation settings
- Customizing screen color
- Setting preferences
- Cleaning the thermostat screen
- Adjusting security settings
- Viewing dealer information
- Advanced Features
- Installer options
- Using the temperature display
- Using the humidity display
- Universal Outputs (U1, U2, U3)
- Universal Inputs (S1, S2, S3, S4)
- Alerts and Diagnostics
- Heat Pump and Backup Heat Operation
- Indoor Air Quality (IAQ) Control
- IAQ Reminders
- Customizable Reminders
- USB Port
- Commercial Features
- Overriding schedules: commercial use
- Setting holiday/event schedules: commercial use
- Setting custom events: commercial use
- Setting holiday schedule: commercial use
- Setting holiday override: commercial use
- Initiating occupancy mode: commercial use
- Ramp Rates
- Custom Names
- Remote Setback
- Economizer and Time of Day (TOD) Operation
- Pre-Occupancy Purge
- Battery Replacement
- Optional Accessories
- Portable Comfort Control
- Remote Indoor Sensors
- Backup Control
- Replacing a Thermostat
- Replacing an Equipment Interface Module
- Wiring
- EIM Wiring Diagrams
- THX9321 Thermostat Wiring Diagrams
- THX9321 Thermostat Wiring Diagrams Using Universal Relays to Control Heating or Cooling
- Wiring IAQ Equipment or a Heat/Cool Stage to the Universal Terminals
- Economizer Module Wiring Diagrams
- Wiring C7089U1006 Outdoor Sensor
- Wiring guide — Wired Indoor Sensors
- Zoning
- Troubleshooting
- Regulatory Information
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—02 98
Cool Differential
The indoor temperature must rise to the selected differential
setting before the thermostat turns on the stage of cooling. For
example, if stage 2 is set to 2 °F (1.0 °C), the indoor
temperature must be 2 °F (1.0 °C) away from the setpoint
before stage 2 turns on. When set to Comfort, the thermostat
uses the stage cooling as needed to keep the indoor
temperature within 1 °F (0.5 °C) degree of the setpoint. The
thermostat turns on stage 2 (or the next stage) when the
capacity on stage 1 reaches 90%.
TO CHANGE DIFFERENTIAL SETTINGS
1. Select Advanced Options to view/adjust differentials
between all stages.
Fig. 192.
2. Default is Comfort. Adjust differentials as needed.
Fig. 193.
Backup Heat Differential (Droop)
A Backup Heat Differential is available for any system with 2
heating types. For example:
• Heat Pumps with any type of Backup Heat
• Radiant Heat with any type of Backup Heat
• Hot Water Fan Coil with any type of Backup Heat
The Backup Heat Differential restricts backup heat during the
following conditions:
• Normal Operation
• Manual Setpoint Changes
The options are:
• Comfort – keeps temperature within 1 degree of the
setpoint.
• 2 to 15 °F – Backup heat is not used unless the indoor
temperature drops to the selected Backup Heat Differential.
For example, if the Backup Heat differential is set to 2 °F
(1.0 °C), the indoor temperature must be 2 °F (1.0 °C) away
from the setpoint before the backup heat turns on.
NORMAL OPERATION
When the Backup Heat Differential is set to Comfort, the
thermostat uses backup heat as needed to keep the indoor
temperature within 1 °F (0.5 °C) of the setpoint.
When the Backup Heat Differential is set to 2 °F or higher,
backup heat is not used unless the indoor temperature drops
to the Backup Heat Differential setting or the Backup Heat
Upstage Timer expires, whichever occurs first. The upstage
timer starts when the highest stage of the previous equipment
type turns on.
MANUAL TEMPERATURE CHANGE
When the Backup Heat Differential is set to Comfort, the
thermostat uses backup heat as needed to keep the indoor
temperature within 1 °F (0.5 °C) of the setpoint.
When the Backup Heat Differential is set to 2 °F or higher, if the
primary heat is making progress as expected, backup heat will
not be used to reach the new setpoint. Set to a higher number
to use less backup heat (a greater difference between the
current indoor temperature and the new setpoint is required to
turn on backup heat). See notes below.
PROGRAMMED RECOVERY
If the primary heat is making progress as expected, backup
heat will not be used to reach the setpoint of the next program
period. Backup heat is always restricted during a programmed
recovery when the Adaptive Intelligent Recovery feature is
used. See note below.
NOTE: During a programmed recovery (or when the tem-
perature setpoint is changed by the user), the
thermostat waits to turn on the backup heat
depending on system performance, load condi-
tions and how many degrees the temperature set-
point is changed. Backup heat will be used ONLY
when the temperature is not rising quickly
enough to reach the setpoint in a reasonable time.
NOTE: If the backup heat was used in the last 2 hours
because the primary heat was not able to main-
tain the setpoint, the thermostat may turn on the
backup heat earlier when the user raises the set-
point. This does NOT apply to heat pumps with
fossil fuel backup heat.
TO CHANGE BACKUP HEAT DIFFERENTIAL (DROOP)
SETTINGS
1. Select Advanced Options or Basic Options to view/adjust
Backup Heat Differential settings.
Fig. 194.