Prestige and VisionPRO EIM Spec Sheet 2013
Table Of Contents
- Application
- Features
- Contents
- Specifications
- System Installation
- Installation Options
- Guidelines for Installing RedLINK Devices
- Installing Equipment Interface Module (if used)
- Wiring 24 Vac Common
- Selecting Discharge and Return Air Temperature Sensor Mounting Locations
- Selecting Return Air Temperature Sensor Mounting Location
- Installing Discharge and Return Air Temperature Sensors
- Selecting Thermostat Location
- Installing Wallplate
- Power Optional REDLINK™ Accessories
- Performing Initial Setup
- Linking Thermostat to Equipment Interface Module (if used)
- Linking RedLINK™ Accessories
- Completing Initial Setup
- Adding RedLINK Accessories to the Thermostat
- Locating the Connect Buttons on RedLINK Accessories
- Finding Your Password (Date Code) to Access Installer Options
- Installer Options
- Making Changes to Installer Setup
- Installer Tests
- Operation
- Setting the time/date
- Setting the fan
- Setting system mode
- Preset Energy-Saving Schedules
- Adjusting program schedules
- Overriding schedules: residential use
- Overriding schedules: commercial use
- Viewing equipment status
- Setting vacation hold: residential use
- Setting holiday/event schedules: commercial use
- Setting custom events: commercial use
- Setting holiday schedule: commercial use
- Setting holiday override: commercial use
- Initiating occupancy mode: commercial use
- Remote setback: commercial use
- Adjusting humidification settings
- Adjusting dehumidification settings: residential use
- Adjusting dehumidification settings: commercial use
- Adjusting ventilation settings
- Customizing screen color
- Setting preferences
- Cleaning the thermostat screen
- Adjusting security settings
- Viewing dealer information
- Advanced Features
- Installer options
- Using the temperature display
- Using the humidity display
- Universal Outputs (U1, U2, U3)
- Universal Inputs (S1, S2, S3, S4)
- Alerts and Diagnostics
- Heat Pump and Backup Heat Operation
- Indoor Air Quality (IAQ) Control
- IAQ Reminders
- Customizable Reminders
- USB Port
- Commercial Features
- Overriding schedules: commercial use
- Setting holiday/event schedules: commercial use
- Setting custom events: commercial use
- Setting holiday schedule: commercial use
- Setting holiday override: commercial use
- Initiating occupancy mode: commercial use
- Ramp Rates
- Custom Names
- Remote Setback
- Economizer and Time of Day (TOD) Operation
- Pre-Occupancy Purge
- Battery Replacement
- Optional Accessories
- Portable Comfort Control
- Remote Indoor Sensors
- Backup Control
- Replacing a Thermostat
- Replacing an Equipment Interface Module
- Wiring
- EIM Wiring Diagrams
- THX9321 Thermostat Wiring Diagrams
- THX9321 Thermostat Wiring Diagrams Using Universal Relays to Control Heating or Cooling
- Wiring IAQ Equipment or a Heat/Cool Stage to the Universal Terminals
- Economizer Module Wiring Diagrams
- Wiring C7089U1006 Outdoor Sensor
- Wiring guide — Wired Indoor Sensors
- Zoning
- Troubleshooting
- Regulatory Information
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—02 46
4080 Outdoor
Temperature used
with Maximum
Cool Recovery
Ramp Rate
Off
-20° F to 100°F
70° F Commercial No Off: The cooling system will begin recovery
at the time that is scheduled.
When a Maximum Recovery Ramp Rate is
set, the thermostat will begin recovery
early to ensure the temperature is reached
at the scheduled time.
Set a Maximum Recovery Ramp Rate
based on the rate that the cooling system
can recover at for a mild day in your region.
Default setting is 6° F / hour.
Set an Outdoor Temperature that is
representative of a mild day in your region
to be associated with the Maximum
Recovery Ramp Rate.
The thermostat will begin recovery at the
optimal time based on a calculated ramp
rate, allowing the system to recover on
time and save energy during changing
outdoor conditions.
During recovery, the setpoint changes at a
rate in degrees per hour depending on the
outdoor temperature.
4090 Adaptive Intelligent
Recovery
No
Yes
Yes Residential No No: The system will begin heating or
cooling recovery at the scheduled time.
Yes: The thermostat will begin heating or
cooling recovery early to ensure that the
temperature is reached at the scheduled
time. The thermostat will adjust the start
time of the equipment based on how
quickly the scheduled temperature was
reached on previous days.
4100 Minimum Cool
Setpoint
50° F to 99° F
50° F Both No The user cannot set the temperature below
this level.
4100 Maximum Heat
Setpoint
40° F to 90° F
90° F Both No The user cannot set the temperature above
this level.
4110 Keypad Lockout
Unlocked
Partially Locked
Fully Locked
Unlocked Both No Unlocked: User has access to all
thermostat settings.
Partially Locked: User can modify only
temperature settings.
Fully Locked: User cannot modify any
settings.
4120 Residential:
Entry / Exit Remote
- Home Cool
Setpoint
Commercial:
Entry / Exit Remote
- Occupied Cool
Setpoint
None
50° F to 99° F
Note: setpoint is limited based on
setting at ISU 4100.
75° F Both No The thermostat maintains this Cool setting
when the user presses Home / Occupied at
the Entry / Exit Remote. Select None to
delete this temperature setting. The
thermostat only responds to the Entry / Exit
Remote if a temperature is pre-set at this
screen. See “Wireless Entry/Exit Remote”
beginning on page 128.
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes