Prestige and VisionPRO EIM Spec Sheet 2013

Table Of Contents
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
31 68-0311—02
3020 Finish With High
Cool Stage
No
Yes
No Both No ISU 3010 Temperature Control Options
must be set to Advanced to view or adjust
Finish With High Cool Stage.
This ISU is only displayed when the
thermostat is set for 2 or more cool stages.
When set to Yes, this feature keeps the
high stage of the cooling equipment
running until the desired setpoint is
reached.
3021 Finish With High
Heat Stage
No
Yes
No Both No ISU 3010 Temperature Control Options
must be set to Advanced to view or adjust
Finish With High Heat Stage.
This ISU is only displayed when the
thermostat is set for 2 or more heat stages.
When set to Yes, this feature keeps the
high stage of the heating equipment
running until the desired setpoint is
reached.
3030 Staging Control -
Cool Differential
Stage 2
Comfort
1.0° F to 3.5° F from setpoint (in
0.5° F increments)
Comfort Both No ISU 3010 Temperature Control Options
must be set to Advanced to view or adjust
this ISU.
This ISU is only displayed when the
thermostat is set to 2 cool stages.
The indoor temperature must rise to the
selected differential setting before the
thermostat turns on the stage of cooling.
For example, if stage 2 is set to 2° F (1.0°
C), the indoor temperature must be 2° F
(1.0° C) away from the setpoint before
stage 2 turns on. When set to Comfort, the
thermostat uses the stage of cooling as
needed to keep the indoor temperature
within 1° F (0.5° C) degree of the setpoint.
3030 Staging Control -
Cool Differential
Stage 3
Comfort
1.0°F - 4.0°F from setpoint (in
0.5° F increments)
Comfort Commercial No ISU 3010 Temperature Control Options
must be set to Advanced to view or adjust
this ISU.
This ISU is only displayed when the
thermostat is set to 3 cool stages.
The indoor temperature must rise to the
selected differential setting before the
thermostat turns on the stage of cooling.
For example, if stage 3 is set to 2° F (1.0°
C), the indoor temperature must be 2° F
(1.0° C) away from the setpoint before
stage 3 turns on. When set to Comfort, the
thermostat uses the stage of cooling as
needed to keep the indoor temperature
within 1° F (0.5° C) degree of the setpoint.
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes